Plug-in suppressor module - WAGO (788 series) - supply voltage 110-230Vac - Plug-in mounting - IP20 - equivalent to 788148

Specifications

  • Primary brand: WAGO
  • Functions: Plug-in suppressor module
  • Supply voltage (AC): 110-230Vac
  • Mounting mode: Plug-in
  • Dimensions: H15.7mm x W15mm x D10mm
  • Ambient air temperature for operation: -25°C...+70°C
  • Ambient air temperature for storage: -40°C...+70°C
  • Customs Tariff Number: 85369010000
  • eClass code: 27-37-16-01
  • ETIM code: EC002586
  • GTIN code: 4050821583547
  • Order code / Manufacturer SKU: 788-148
  • Manufacturer product status: Commercialized
  • Equivalent to: 788148
  • EAN code: 4050821583547
  • Compliant with standard(s): EN 60664-1|General approvals|- EAC - GZO Almaty Standart - TP TC 004/2011 - certificate EAC CoC 03084|RoHS compliant
  • Location of origin: Germany
  • Level 1 category: Electrical components
  • Level 2 category: Electrical circuits protection
  • Level 3 category: Surge Protection Devices (SPD)
  • Product title: Plug-in suppressor module - WAGO

Commercial data

  • Country of origin: DE
  • Customs tariff number: 85369010000
  • ECCN: NO US CLASSIFICATION
  • eCl@ss 10.0: 27-37-16-01
  • eCl@ss 9.0: 27-37-16-92
  • ETIM 8.0: EC002586
  • ETIM 9.0: EC002586
  • GTIN: 4050821583547
  • Packaging type: box
  • Product Group: 6 (INTERFACE ELECTRONIC)
  • PU (SPU): 50 (25) pcs

Environmental Product Compliance

  • RoHS Compliance Status: Compliant,No Exemption

Environmental requirements

  • Ambient temperature (operation at UN): -25 … +70 °C
  • Ambient temperature (storage): -40 … +70 °C

Material data

Mechanical data

  • Mounting type: Pluggable module

Notes

  • Note: To guarantee safe operation, residual voltages (due to the cable capacitance of long connection lines or leakage currents of semi-conductor switches and their protective circuits) must be lower than the release voltage of the relays.
    For DC relays, the release voltage is specified with ≤ 5% of the nominal voltage; for AC relays, it is 15% of the nominal voltage (per VDE 0435).
    The relay may not reset if a high residual voltage exists. Depending on the reason for the residual voltage, changing the cable routing or a parallel connection of an RC element could remedy this situation.

Physical data

  • Depth: 10 mm / 0.394 inches
  • Height from the surface: 15.7 mm / 0.618 inches
  • Width: 15 mm / 0.591 inches

Safety and protection

  • Protection type: IP20

Standards and specifications

  • Standards/specifications: EN 60664-1

Technical data

  • Control circuit - Nominal input current at UN: 0
  • Module characteristics - Capacitance: 100 nF
  • Module characteristics - Resistor: 470Ω
  • Operating data - Current consumption at UN: 7.2 mA (230 VAC; 50 Hz); 3.6 mA (115 VAC; 50 Hz)
  • Operating data - Nominal mains frequency range: 50 … 60 Hz
  • Operating data - Nominal operating voltage: 230 VAC
  • Operating data - Operating voltage: 0 … 230 VAC