Wago - 753-479
$546.40
Sale price
$546.40
Regular price
Pluggable analog input slice unit module - WAGO (753 series) - 2AI; +-10Vdc; Diff - 2I/O [2AI (2 x analog inputs (-10...+10Vdc; Differential; 14-bits / 1ms conversion; 2-wire; with 5kHz filter))] - supply voltage 5Vdc (supplied by system) - with spring CAGE CLAMP connections - DIN-35 rail mounting (12mm width) - IP20 - rated for 0°C...+55°C ambient - equivalent to 753479
Specifications
- Primary brand: WAGO
- Functions: Pluggable analog input slice unit module
- Supply voltage (DC): 5Vdc (supplied by system)
- Display: LED (A/C) green -- Function AI 1 / AI 2|LED (B/D) red -- Error AI 1 / AI 2
- Connection type: spring CAGE CLAMP connections
- Mounting mode: DIN-35 rail
- Analog inputs: 2 x analog inputs (-10...+10Vdc; Differential; 14-bits / 1ms conversion; 2-wire; with 5kHz filter)
- Measurement accuracy: +-0.05% (measuring error)|+-0.01% (temperature error)
- Dimensions: H100mm x W12mm x D69.8mm
- Net Width (mm): 12mm
- Material: Polycarbonate (PC) / Polyamide (PA) 6.6 housing
- Ambient air temperature for operation: 0°C...+55°C
- Ambient air temperature for storage: -40°C...+85°C
- Humidity: 95% relative humidity (RH; non-condensing)
- Mechanical resistance: Vibration resistance according to EN 60068-2-6 -- 4g|Shock resistance according to EN 60068-2-27 --15g
- Current consumption: 100mA (5Vdc; system supply)
- ETIM code: EC001596
- Customs Tariff Number: 85389099990
- eClass code: 27-24-26-01
- GTIN code: 4045454510756
- Order code / Manufacturer SKU: 753-479
- Manufacturer product status: Commercialized
- Equivalent to: 753479
- EAN code: 4045454510756
- Compliant with standard(s): CE|EMC immunity to interference|- EN 61000-6-2|- marine applications|EMC emission of interference|- EN 61000-6-4|- marine applications|General approvals|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03083|- KC - National Radio Research Agency - Article 58-2 / Clause 3 - certificate MSIP-REM-W43-AIM750|- UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 508 - certificate E175199|Declarations of conformity and manufacturer's declarations|- EU-Declaration of Conformity - WAGO GmbH & Co. KG|- UK-Declaration of Conformity - WAGO GmbH & Co. KG|Approvals for marine applications|- ABS - American Bureau of Shipping - certificate 22-2219060|- BSH - Bundesamt fuer Seeschifffahrt und Hydrographie - certificate 1104|- BV - Bureau Veritas S.A. - certificate 13453/E0 BV|- DNV - DNV GL SE - DNV-CG-0339 / Aug.2021 - certificate TAA0000194|- KR - Korean Register of Shipping - certificate KR HMB05880-AC001|- LR - Lloyds Register EMEA - certificate LR22180952TA|- PRS - Polski Rejestr Statkow - certificate TE/1101/880590/23|- RINA - RINA Germany GmbH - certificate ELE343521XG001|Approvals for hazardous areas|- ATEX - TUV Nord Cert GmbH - EN 60079-0 - certificate TUV14ATEX148929X (II 3 G Ex ec IIC T4 Gc)|- CCCEx - CQST/CNEx - CNCA-C23-01 - certificate 2020312310000213 (Ex ec IIC T4 Gc)|- IECEx - TUV Nord Cert GmbH - IEC 60079-0 - certificate IECEx TUN 14.0035 X (Ex ec IIC T4 Gc)|- INMETRO - TUV Rheinland do Brasil Ltda. - IEC 60079-0 - certificate TUV 12.1297 X|- UKEx - WAGO GmbH & Co. KG - EN 60079-0 - certificate UKCA_WAGO22UKEX003X_ec|- UL - Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS) - UL 121201 - certificate E198726|RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
- Location of origin: Germany
- Degree of pollution: 2
- Level 1 category: Automation components
- Level 2 category: Programmable Logic Controllers & components
- Level 3 category: I-O Units
- Product title: Pluggable analog input slice unit module - WAGO
Commercial data
- Country of origin: DE
- Customs tariff number: 85389099990
- ECCN: NO US CLASSIFICATION
- eCl@ss 10.0: 27-24-26-01
- eCl@ss 9.0: 27-24-26-01
- ETIM 8.0: EC001596
- ETIM 9.0: EC001596
- GTIN: 4045454510756
- Packaging type: box
- Product Group: 15 (I/O System)
- PU (SPU): 1 pcs
Connection data
- Connectable conductor materials: Copper
- Connection technology: inputs/outputs: 6 x CAGE CLAMP®
- Connection type 1: Inputs/Outputs
- Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Strip length: 9 … 10 mm / 0.35 … 0.39 inches
Environmental Product Compliance
- CAS-No.: 1303-86-2|1317-36-8|25550-51-0|7439-92-1
- REACH Candidate List Substance: 4-Methyl-1,2-cyclohexanedicarboxylic anhydride|Diboron trioxide|Lead|Lead monoxide
- RoHS Compliance Status: Compliant,With Exemption
- RoHS Exemption: 6(c)|7(a)|7(c)-I|7(c)-II
- SCIP notification number (Austria): 51ea0e1b-2924-4688-b6e4-73d1db8ef0d4
- SCIP notification number (Belgium): 016c9bf7-d298-4a25-bede-09196e34eb31
- SCIP notification number (Bulgaria): 94abdebc-2562-4410-9fa3-f41417c09539
- SCIP notification number (Czech Republic): 58dfadc1-aa8c-4d04-a03c-e1410f104087
- SCIP notification number (Denmark): d35c0e66-0de5-4709-a364-c0ec157a98b2
- SCIP notification number (Finland): 15361080-4bc0-4682-bf1e-d366ac53796c
- SCIP notification number (France): 99d6e565-25cd-4abf-98d4-05141363ea18
- SCIP notification number (Germany): 71f81048-17ea-4b96-907a-0896c01923a9
- SCIP notification number (Hungary): 4810d655-76ed-43d3-9d4d-71c6ec65d3ce
- SCIP notification number (Italy): 8d042089-2c4a-4617-9fdf-b0004cadb745
- SCIP notification number (Netherlands): 368dcbd5-a930-4ee9-ac8e-7c3b04c9360f
- SCIP notification number (Poland): 93d966c2-7b45-43bb-b1d5-f0a284d85d45
- SCIP notification number (Romania): bfb54203-4064-4eac-ac50-139037b9da83
- SCIP notification number (Sweden): 0d06e325-e0ce-4794-a960-ee2caa7f8da7
Environmental requirements
- Ambient temperature (operation): 0 … +55 °C
- Ambient temperature (storage): -40 … +85 °C
- EMC emission of interference: per EN 61000-6-4, marine applications
- EMC immunity to interference: per EN 61000-6-2, marine applications
- Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
- Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
- Operating altitude: 0 … 2000 m / 0 … 6562 ft
-
Permissible H2S contaminant concentration at a relative humidity
75 %: 10ppm -
Permissible SO2 contaminant concentration at a relative humidity
75 %: 25ppm - Pollution degree: 2 per IEC 61131-2
- Protection type: IP20
- Relative humidity (without condensation): 95%
- Shock resistance: 15g per IEC 60068-2-27
- Vibration resistance: 4g per IEC 60068-2-6
Material data
- Color: light gray
- Conformity marking: CE
- Fire load: 0.882MJ
- Housing material: Polycarbonate; polyamide 6.6
- Weight: 42.1g
Mechanical data
- Mounting type: DIN-35 rail
- Pluggable connector: Pluggable
Notes
-
Note:
Pluggable connectors and coding fingers (753 Series) are not included.
Physical data
- Depth: 69.8 mm / 2.748 inches
- Depth from upper-edge of DIN-rail: 62.6 mm / 2.465 inches
- Height: 100 mm / 3.937 inches
- Width: 12 mm / 0.472 inches
Technical data
- Admissible continuous overload: 60V
- Conversion method: SAR (Successive Approximation Register)
- Crosstalk attenuation: 80dB
- Current consumption (5 V system supply): 100mA
- Data width: 2 x 16-bit data; 2 x 8-bit control/status (optional)
- Indicators: LED (A, C) green: Function AI 1, AI 2; LED (B, D) red: Error AI 1, AI 2
- Input filter: Low pass (1st order), fG = 5 kHz
- Internal resistance: 1000kΩ
- Isolation: 500 V system/field or channel/channel
- Measured value acquisition: Time synchronous within the module
- Measurement error (reference temperature): 25°C
- Measurement error over entire temperature range: ≤ 0.4 %
- Measurement error, deviation (max.) from the upper-range value: 0.05%
- Measurement range overflow/underflow: Status byte and LED
- Monotonicity without error code: yes
- Number of analog inputs: 2
- Operating mode: Continuously sampling (default)
- Protective device: RC circuit
- Resolution [bit]: 14bits
- Sampling delay (channel/channel): 1µs
- Sampling delay (module): 1ms
- Sampling duration: 5µs
- Sampling repetition time: 1ms
- Sensor connection: 2 x (2-wire)
- Signal characteristics: Differential
- Signal type: Voltage
- Signal type (voltage): -10 … +10 VDC
- Supply voltage (system): 5 VDC; via data contacts
- Temperature error (max.) of the upper-range value: 0.01%/K
- Total number of channels (module): 2
- Value of the least significant bit (LSB): 1.2 mV