Wago - 750-484

$1,322.00
Sale price  $1,322.00 Regular price 

Wago - 750-484

$1,322.00
Sale price  $1,322.00 Regular price 

Intrinsically-safe analog input slice unit module - WAGO (750 series) - 2AI; 4-20mA HART; Ex i - 2I/O [2AI (2 x analog inputs (4-20mA; Single-ended; 12-bits / 10ms conversion / HART; 2-wire))] - with HART communication capability - supply voltage 5Vdc (supplied by system) - with spring CAGE CLAMP connections - DIN-35 rail mounting (24mm width) - IP20 - rated for 0°C...+55°C ambient - equivalent to 750484

Specifications

  • Primary brand: WAGO
  • Functions: Intrinsically-safe analog input slice unit module|Configuration options|- WAGO-I/O-CHECK|- e!COCKPIT
  • Supply voltage (DC): 5Vdc (supplied by system)|24Vdc fixed suppl. to field sensing devices
  • Display: LED (A/E) green -- Function HART 1/HART 2|LED (B/F) red -- Error HART 1/HART 2
  • Connection type: spring CAGE CLAMP connections
  • Protection functions: wire-break protection|overvoltage protection|reverse polarity protection
  • Mounting mode: DIN-35 rail
  • Analog inputs: 2 x analog inputs (4-20mA; Single-ended; 12-bits / 10ms conversion / HART; 2-wire)
  • Measurement accuracy: +-0.2% (measuring error)|+-0.01% (temperature error)
  • Dimensions: H100mm x W24mm x D67.8mm
  • Net Width (mm): 24mm
  • Material: Polycarbonate (PC) / Polyamide (PA) 6.6 housing
  • Ambient air temperature for operation: 0°C...+55°C
  • Ambient air temperature for storage: -25°C...+85°C
  • Humidity: 95% relative humidity (RH; non-condensing)
  • Mechanical resistance: Vibration resistance according to EN 60068-2-6 -- 4g|Shock resistance according to EN 60068-2-27 --15g
  • Current consumption: 25mA (5Vdc; system supply)|26mA (field supply; no external load)
  • Power consumption: 1.6W
  • ETIM code: EC001596
  • eClass code: 27-24-26-01
  • Customs Tariff Number: 85389099990
  • Power dissipation/losses: 0.62W
  • Order code / Manufacturer SKU: 750-484
  • Manufacturer product status: Commercialized
  • Equivalent to: 750484
  • EAN code: 4017332317603
  • Compliant with standard(s): CE|EMC immunity to interference|- EN 61000-6-2|- marine applications|EMC emission of interference|- EN 61000-6-3|- marine applications|General approvals|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03083|- KC - National Radio Research Agency - Article 58-2 / Clause 3 - certificate MSIP-REM-W43-AIM750|- UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 508 - certificate E175199|Declarations of conformity and manufacturer's declarations|- EU-Ex-Declaration of Conformity - WAGO GmbH & Co. KG|Approvals for marine applications|- ABS - American Bureau of Shipping - certificate 22-2219060|- BV - Bureau Veritas S.A. - certificate 30389/C0 BV|- DNV - DNV GL SE - DNV-CG-0339 / Aug.2021 - certificate TAA0000194|- KR - Korean Register of Shipping - certificate KR HMB05880-AC001|- LR - Lloyds Register EMEA - certificate LR22180952TA|- PRS - Polski Rejestr Statkow - certificate TE/1101/880590/23|- RINA - RINA Germany GmbH - certificate ELE343521XG001|Approvals for hazardous areas|- AEx - UL International Germany GmbH - UL 60079 - certificate E480271|- ATEX - TUV Nord Cert GmbH - EN 60079-0 - certificate TUV12ATEX106032X (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)|- CCC - CNEX - CNCA-C23-01 - certificate 2020312310000211 (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)|- IECEx - TUV Nord Cert GmbH - IEC 60079 - certificate IECEx TUN12.0039X (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)|- INMETRO - TUV Rheinland do Brasil Ltda. - certificate TUV_14.1911_X|- UKEx - Element Materials Technology UK - certificate EMA21UKEX0069X|- UL - Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS) - UL 121201 - certificate E198726|RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
  • Location of origin: Germany
  • Degree of pollution: 2
  • Level 1 category: Automation components
  • Level 2 category: Programmable Logic Controllers & components
  • Level 3 category: I-O Units
  • Product title: Intrinsically-safe analog input slice unit module - WAGO

Commercial data

  • Country of origin: DE
  • Customs tariff number: 85389099990
  • ECCN: NO US CLASSIFICATION
  • eCl@ss 10.0: 27-24-26-01
  • eCl@ss 9.0: 27-24-26-01
  • ETIM 8.0: EC001596
  • ETIM 9.0: EC001596
  • Packaging type: Box
  • Product Group: 15 (I/O System)
  • PU (SPU): 1 pcs

Connection data

  • Connectable conductor materials: Copper
  • Connection technology: inputs/outputs: 6 x CAGE CLAMP®
  • Connection type 1: Inputs/outputs
  • Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Strip length: 8 … 9 mm / 0.31 … 0.35 inches

Environmental Product Compliance

  • CAS-No.: 11120-22-2|1303-86-2|1317-36-8|7439-92-1|79-94-7|872-50-4
  • REACH Candidate List Substance: 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol|Diboron trioxide|Lead|Lead monoxide|Lead silicate|N-Methylpyrrolidone
  • RoHS Compliance Status: Compliant,With Exemption
  • RoHS Exemption: 6(c)|7(a)|7(c)-I|7(c)-II
  • SCIP notification number (Austria): 6e29c8ee-bb97-4371-a284-a442d1a1eef5
  • SCIP notification number (Belgium): 7deed5f3-a54b-4363-a123-d6a515c78a9f
  • SCIP notification number (Bulgaria): b0643f05-8768-49bd-adcc-22cfdd43a1ed
  • SCIP notification number (Czech Republic): c5777387-8a65-481c-bd87-ffe09d2c209f
  • SCIP notification number (Denmark): 2b9bc2cd-58eb-4194-8780-6b4a39c20d10
  • SCIP notification number (Finland): 164cfd47-cb02-474c-a02d-441afb09b259
  • SCIP notification number (France): 011829da-5f12-460c-b615-e6b9fa6b64b0
  • SCIP notification number (Germany): 687d5fb4-ebe7-4022-b885-833d3eea5977
  • SCIP notification number (Hungary): a7e731d3-8a9e-4b68-83ee-21569a78cfcc
  • SCIP notification number (Italy): 2269238f-32e4-42b8-9d2e-1d9bf3bf60f3
  • SCIP notification number (Netherlands): bb3b72a4-7f06-4dc7-b15d-06a6a7e00d63
  • SCIP notification number (Poland): c15e2775-6b9f-4fde-b8b4-fe643d4322b7
  • SCIP notification number (Romania): 900dca82-746b-46a3-8f53-d4ce20d0d9cb
  • SCIP notification number (Sweden): 0f5aabb7-ba5a-4972-9ff2-7ac1a16bbd56

Environmental requirements

  • Ambient temperature (operation): 0 … +55 °C
  • Ambient temperature (storage): -25 … +85 °C
  • EMC emission of interference: per EN 61000-6-3, marine applications
  • EMC immunity to interference: per EN 61000-6-2, marine applications
  • Exposure to pollutants: per IEC 60068-2-42 and IEC 60068-2-43
  • Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
  • Operating altitude: 0 … 2000 m / 0 … 6562 ft
  • Permissible H2S contaminant concentration at a relative humidity 75 %: 10ppm
  • Permissible SO2 contaminant concentration at a relative humidity 75 %: 25ppm
  • Pollution degree: 2 per IEC 61131-2
  • Protection type: IP20
  • Relative humidity (without condensation): 95%
  • Shock resistance: 15g per IEC 60068-2-27
  • Vibration resistance: 4g per IEC 60068-2-6

Explosion protection

  • Ex standard: EN IEC 60079-0, -7, -11
  • Identification: ATEX
    II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
    II (1) D [Ex ia Da] IIIC
    I (M1) [Ex ia Ma] I|IECEx/ INMETRO
    Ex ec [ia Ga] IIC T4 Gc
    [Ex ia Da] IIIC
    [Ex ia Ma] I|cULus (Zone classified)
    Cl I Zn 2 AEx nA [ia Ga] IIC T4 Gc
    Cl I Zn 2 AEx nA [ia IIIC] IIC T4 Gc
    Ex nA [ia Ga] IIC T4 Gc X
    Ex nA [ia IIIC] IIC T4 Gc X|cULus (Devision classified)
    Class I, Div. 2, Group A B C D, T4
  • Reactances (note): Reactances without accounting for the concurrence of capacitance (Co) and inductance (Lo)
  • Reactances Ex ia I: Lo = 36 mH; Co = 3.49 µF
  • Reactances Ex ia IIA: Lo = 38 mH; Co = 2.2 μF
  • Reactances Ex ia IIB: Lo = 15 mH; Co = 670 nF
  • Reactances Ex ia IIC: Lo = 1.5 mH; Co = 87 nF
  • Safety-relevant data (circuit): Uo = 27.3 V; Io = 92.7 mA; Po = 630 mW; linear characteristic curve

Material data

  • Color: blue
  • Conformity marking: CE
  • Fire load: 2.034MJ
  • Housing material: Polycarbonate; polyamide 6.6
  • Weight: 92g

Mechanical data

  • Mounting type: DIN-35 rail

Notes

  • Note:

    The analog input module must only be operated via 24 VDC Ex i!

    General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals!

Physical data

  • Depth: 67.8 mm / 2.669 inches
  • Depth from upper-edge of DIN-rail: 60.6 mm / 2.386 inches
  • Height: 100 mm / 3.937 inches
  • Width: 24 mm / 0.945 inches

Technical data

  • Configuration options: WAGO-I/O-CHECK|e!COCKPIT
  • Conversion time (typ.): 10ms
  • Current carrying capacity (power jumper contacts): 1A
  • Current consumption (5 V system supply): 25mA
  • Current consumption, field supply (module with no external load): 26mA
  • Data width: 2 x 2-byte data; 2 x 2-byte data + 2n x 4-byte data (n = number of dynamic variables); 2 x 2-byte data + 6-byte mailbox
  • Diagnostics: Wire break, measurement range overflow
  • HART devices per channel: 1 device (single-drop, no multi-drop)
  • HART modems per channel: 1 modem (no multiplex)
  • Indicators: LED (A, E) green: Function HART 1, HART 2; LED (B, F) red: Error HART 1, HART 2
  • Input filter: parameterizable
  • Input filter: parametrizable (channel by channel): Yes
  • Intrinsically safe Ex i: Yes
  • Isolation: 300 VAC system/supply
  • Item description: 2-Channel Analog Input; 4 … 20 mA HART
  • Measurement error (reference temperature): 25°C
  • Measurement error, deviation (max.) from the upper-range value: 0.2%
  • Number of analog inputs: 2
  • Number of incoming power jumper contacts: 2
  • Number of outgoing power jumper contacts: 2
  • Overvoltage protection: 30 V, reverse polarity protected
  • Power consumption Pmax.: 1.60 W (with slaves (20 mA))
  • Power loss Pl: 0.62 W (without slaves)
  • Resolution [bit]: 12bits
  • Sensor connection: 2 x (2-wire)
  • Sensor supply: 16.5 VDC
  • Signal characteristics: Single-ended
  • Signal type: Current
  • Signal type (current): 4 … 20 mADC
  • Supply voltage (field): 24 VDC; (Ex i power supply: Uo = max. 26.8 V); via power jumper contacts (power supply via blade contact; transmission via spring contact)
  • Supply voltage (system): 5 VDC; via data contacts
  • Temperature error (max.) of the upper-range value: ±0.01%/K
  • Total number of channels (module): 2