Wago - 750-484
$1,322.00
Sale price
$1,322.00
Regular price
Intrinsically-safe analog input slice unit module - WAGO (750 series) - 2AI; 4-20mA HART; Ex i - 2I/O [2AI (2 x analog inputs (4-20mA; Single-ended; 12-bits / 10ms conversion / HART; 2-wire))] - with HART communication capability - supply voltage 5Vdc (supplied by system) - with spring CAGE CLAMP connections - DIN-35 rail mounting (24mm width) - IP20 - rated for 0°C...+55°C ambient - equivalent to 750484
Specifications
- Primary brand: WAGO
- Functions: Intrinsically-safe analog input slice unit module|Configuration options|- WAGO-I/O-CHECK|- e!COCKPIT
- Supply voltage (DC): 5Vdc (supplied by system)|24Vdc fixed suppl. to field sensing devices
- Display: LED (A/E) green -- Function HART 1/HART 2|LED (B/F) red -- Error HART 1/HART 2
- Connection type: spring CAGE CLAMP connections
- Protection functions: wire-break protection|overvoltage protection|reverse polarity protection
- Mounting mode: DIN-35 rail
- Analog inputs: 2 x analog inputs (4-20mA; Single-ended; 12-bits / 10ms conversion / HART; 2-wire)
- Measurement accuracy: +-0.2% (measuring error)|+-0.01% (temperature error)
- Dimensions: H100mm x W24mm x D67.8mm
- Net Width (mm): 24mm
- Material: Polycarbonate (PC) / Polyamide (PA) 6.6 housing
- Ambient air temperature for operation: 0°C...+55°C
- Ambient air temperature for storage: -25°C...+85°C
- Humidity: 95% relative humidity (RH; non-condensing)
- Mechanical resistance: Vibration resistance according to EN 60068-2-6 -- 4g|Shock resistance according to EN 60068-2-27 --15g
- Current consumption: 25mA (5Vdc; system supply)|26mA (field supply; no external load)
- Power consumption: 1.6W
- ETIM code: EC001596
- eClass code: 27-24-26-01
- Customs Tariff Number: 85389099990
- Power dissipation/losses: 0.62W
- Order code / Manufacturer SKU: 750-484
- Manufacturer product status: Commercialized
- Equivalent to: 750484
- EAN code: 4017332317603
- Compliant with standard(s): CE|EMC immunity to interference|- EN 61000-6-2|- marine applications|EMC emission of interference|- EN 61000-6-3|- marine applications|General approvals|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03083|- KC - National Radio Research Agency - Article 58-2 / Clause 3 - certificate MSIP-REM-W43-AIM750|- UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 508 - certificate E175199|Declarations of conformity and manufacturer's declarations|- EU-Ex-Declaration of Conformity - WAGO GmbH & Co. KG|Approvals for marine applications|- ABS - American Bureau of Shipping - certificate 22-2219060|- BV - Bureau Veritas S.A. - certificate 30389/C0 BV|- DNV - DNV GL SE - DNV-CG-0339 / Aug.2021 - certificate TAA0000194|- KR - Korean Register of Shipping - certificate KR HMB05880-AC001|- LR - Lloyds Register EMEA - certificate LR22180952TA|- PRS - Polski Rejestr Statkow - certificate TE/1101/880590/23|- RINA - RINA Germany GmbH - certificate ELE343521XG001|Approvals for hazardous areas|- AEx - UL International Germany GmbH - UL 60079 - certificate E480271|- ATEX - TUV Nord Cert GmbH - EN 60079-0 - certificate TUV12ATEX106032X (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)|- CCC - CNEX - CNCA-C23-01 - certificate 2020312310000211 (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)|- IECEx - TUV Nord Cert GmbH - IEC 60079 - certificate IECEx TUN12.0039X (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)|- INMETRO - TUV Rheinland do Brasil Ltda. - certificate TUV_14.1911_X|- UKEx - Element Materials Technology UK - certificate EMA21UKEX0069X|- UL - Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS) - UL 121201 - certificate E198726|RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
- Location of origin: Germany
- Degree of pollution: 2
- Level 1 category: Automation components
- Level 2 category: Programmable Logic Controllers & components
- Level 3 category: I-O Units
- Product title: Intrinsically-safe analog input slice unit module - WAGO
Commercial data
- Country of origin: DE
- Customs tariff number: 85389099990
- ECCN: NO US CLASSIFICATION
- eCl@ss 10.0: 27-24-26-01
- eCl@ss 9.0: 27-24-26-01
- ETIM 8.0: EC001596
- ETIM 9.0: EC001596
- Packaging type: Box
- Product Group: 15 (I/O System)
- PU (SPU): 1 pcs
Connection data
- Connectable conductor materials: Copper
- Connection technology: inputs/outputs: 6 x CAGE CLAMP®
- Connection type 1: Inputs/outputs
- Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Strip length: 8 … 9 mm / 0.31 … 0.35 inches
Environmental Product Compliance
- CAS-No.: 11120-22-2|1303-86-2|1317-36-8|7439-92-1|79-94-7|872-50-4
- REACH Candidate List Substance: 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol|Diboron trioxide|Lead|Lead monoxide|Lead silicate|N-Methylpyrrolidone
- RoHS Compliance Status: Compliant,With Exemption
- RoHS Exemption: 6(c)|7(a)|7(c)-I|7(c)-II
- SCIP notification number (Austria): 6e29c8ee-bb97-4371-a284-a442d1a1eef5
- SCIP notification number (Belgium): 7deed5f3-a54b-4363-a123-d6a515c78a9f
- SCIP notification number (Bulgaria): b0643f05-8768-49bd-adcc-22cfdd43a1ed
- SCIP notification number (Czech Republic): c5777387-8a65-481c-bd87-ffe09d2c209f
- SCIP notification number (Denmark): 2b9bc2cd-58eb-4194-8780-6b4a39c20d10
- SCIP notification number (Finland): 164cfd47-cb02-474c-a02d-441afb09b259
- SCIP notification number (France): 011829da-5f12-460c-b615-e6b9fa6b64b0
- SCIP notification number (Germany): 687d5fb4-ebe7-4022-b885-833d3eea5977
- SCIP notification number (Hungary): a7e731d3-8a9e-4b68-83ee-21569a78cfcc
- SCIP notification number (Italy): 2269238f-32e4-42b8-9d2e-1d9bf3bf60f3
- SCIP notification number (Netherlands): bb3b72a4-7f06-4dc7-b15d-06a6a7e00d63
- SCIP notification number (Poland): c15e2775-6b9f-4fde-b8b4-fe643d4322b7
- SCIP notification number (Romania): 900dca82-746b-46a3-8f53-d4ce20d0d9cb
- SCIP notification number (Sweden): 0f5aabb7-ba5a-4972-9ff2-7ac1a16bbd56
Environmental requirements
- Ambient temperature (operation): 0 … +55 °C
- Ambient temperature (storage): -25 … +85 °C
- EMC emission of interference: per EN 61000-6-3, marine applications
- EMC immunity to interference: per EN 61000-6-2, marine applications
- Exposure to pollutants: per IEC 60068-2-42 and IEC 60068-2-43
- Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
- Operating altitude: 0 … 2000 m / 0 … 6562 ft
-
Permissible H2S contaminant concentration at a relative humidity
75 %: 10ppm -
Permissible SO2 contaminant concentration at a relative humidity
75 %: 25ppm - Pollution degree: 2 per IEC 61131-2
- Protection type: IP20
- Relative humidity (without condensation): 95%
- Shock resistance: 15g per IEC 60068-2-27
- Vibration resistance: 4g per IEC 60068-2-6
Explosion protection
- Ex standard: EN IEC 60079-0, -7, -11
-
Identification: ATEX
II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I|IECEx/ INMETRO
Ex ec [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
[Ex ia Ma] I|cULus (Zone classified)
Cl I Zn 2 AEx nA [ia Ga] IIC T4 Gc
Cl I Zn 2 AEx nA [ia IIIC] IIC T4 Gc
Ex nA [ia Ga] IIC T4 Gc X
Ex nA [ia IIIC] IIC T4 Gc X|cULus (Devision classified)
Class I, Div. 2, Group A B C D, T4 - Reactances (note): Reactances without accounting for the concurrence of capacitance (Co) and inductance (Lo)
- Reactances Ex ia I: Lo = 36 mH; Co = 3.49 µF
- Reactances Ex ia IIA: Lo = 38 mH; Co = 2.2 μF
- Reactances Ex ia IIB: Lo = 15 mH; Co = 670 nF
- Reactances Ex ia IIC: Lo = 1.5 mH; Co = 87 nF
- Safety-relevant data (circuit): Uo = 27.3 V; Io = 92.7 mA; Po = 630 mW; linear characteristic curve
Material data
- Color: blue
- Conformity marking: CE
- Fire load: 2.034MJ
- Housing material: Polycarbonate; polyamide 6.6
- Weight: 92g
Mechanical data
- Mounting type: DIN-35 rail
Notes
-
Note:
The analog input module must only be operated via 24 VDC Ex i!
General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals!
Physical data
- Depth: 67.8 mm / 2.669 inches
- Depth from upper-edge of DIN-rail: 60.6 mm / 2.386 inches
- Height: 100 mm / 3.937 inches
- Width: 24 mm / 0.945 inches
Technical data
- Configuration options: WAGO-I/O-CHECK|e!COCKPIT
- Conversion time (typ.): 10ms
- Current carrying capacity (power jumper contacts): 1A
- Current consumption (5 V system supply): 25mA
- Current consumption, field supply (module with no external load): 26mA
- Data width: 2 x 2-byte data; 2 x 2-byte data + 2n x 4-byte data (n = number of dynamic variables); 2 x 2-byte data + 6-byte mailbox
- Diagnostics: Wire break, measurement range overflow
- HART devices per channel: 1 device (single-drop, no multi-drop)
- HART modems per channel: 1 modem (no multiplex)
- Indicators: LED (A, E) green: Function HART 1, HART 2; LED (B, F) red: Error HART 1, HART 2
- Input filter: parameterizable
- Input filter: parametrizable (channel by channel): Yes
- Intrinsically safe Ex i: Yes
- Isolation: 300 VAC system/supply
- Item description: 2-Channel Analog Input; 4 … 20 mA HART
- Measurement error (reference temperature): 25°C
- Measurement error, deviation (max.) from the upper-range value: 0.2%
- Number of analog inputs: 2
- Number of incoming power jumper contacts: 2
- Number of outgoing power jumper contacts: 2
- Overvoltage protection: 30 V, reverse polarity protected
- Power consumption Pmax.: 1.60 W (with slaves (20 mA))
- Power loss Pl: 0.62 W (without slaves)
- Resolution [bit]: 12bits
- Sensor connection: 2 x (2-wire)
- Sensor supply: 16.5 VDC
- Signal characteristics: Single-ended
- Signal type: Current
- Signal type (current): 4 … 20 mADC
- Supply voltage (field): 24 VDC; (Ex i power supply: Uo = max. 26.8 V); via power jumper contacts (power supply via blade contact; transmission via spring contact)
- Supply voltage (system): 5 VDC; via data contacts
- Temperature error (max.) of the upper-range value: ±0.01%/K
- Total number of channels (module): 2