Skip to product information
Wago - 2857-534
$430.50
Sale price
$430.50
Regular price
Thermocouple threshold value switch with DIP / software configuration + display - WAGO (2857 JUMPFLEX series) - with 1 x analog input (Thermocouples types J; K; E; N; R; S; T; B; C) - supply voltage 16.8-31.2Vdc (24Vdc nom.) - with Push-in CAGE CLAMP spring connections - DIN-35 rail mounting (12.5mm width) - IP20 - rated for -40°C...+70°C ambient - equivalent to 2857534
Specifications
- Primary brand: WAGO
- Functions: Thermocouple threshold value switch
- Design: DIP / software configuration|display
- Supply voltage (DC): 16.8-31.2Vdc (24Vdc nom.)
- Connection type: Push-in CAGE CLAMP spring connections
- Mounting mode: DIN-35 rail
- Digital outputs: 1 x digital output (SPDT (Single Pole Double Throw) rly. contact type; 250Vac; 6A)
- Analog inputs: 1 x analog input (Thermocouples types J; K; E; N; R; S; T; B; C)
- Measurement accuracy: ≤ 0.01%/K (temperature coefficient)
- Dimensions: H110mm x W12.5mm x D107mm
- Net Width (mm): 12.5mm
- Material: Hard Gold-plated Silver-Nickel (AgNi + Au) contacts
- Ambient air temperature for operation: -40°C...+70°C
- Ambient air temperature for storage: -40°C...+85°C
- Current consumption: 40mA (24Vdc; at nominal load)
- Customs Tariff Number: 90303370000
- ETIM code: EC001446
- eClass code: 27-37-18-10
- GTIN code: 4055143242318
- Order code / Manufacturer SKU: 2857-534
- Manufacturer product status: Commercialized
- Equivalent to: 2857534
- EAN code: 4055143242318
- Compliant with standard(s): Safety and protection|- Overvoltage category -- II|CE|EN 50121-3-2|EN 61010-1|EN 61373|EMC immunity to interference|- EN 61000-6-2|- EN 61326-2-3|- EN 50121-3-2|EMC emission of interference|- EN 61000-6-4|- EN 61326-2-3|- EN 50121-3-2|General approvals|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03083|- EAC - GZO Almaty Standart - TP TC 004/2011 - certificate EAC CoC 03084|- UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 61010-2-201 - certificate E175199|Declarations of conformity and manufacturer's declarations|- EU-Declaration of Conformity - WAGO GmbH & Co. KG|RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
- Location of origin: Germany
- Degree of pollution: 2
- Level 1 category: Automation components
- Product title: Thermocouple threshold value switch - WAGO (JUMPFLEX series)
Commercial data
- Country of origin: DE
- Customs tariff number: 90303370000
- ECCN: NO US CLASSIFICATION
- eCl@ss 10.0: 27-37-18-10
- eCl@ss 9.0: 27-37-18-10
- ETIM 8.0: EC001446
- ETIM 9.0: EC001446
- GTIN: 4055143242318
- Packaging type: bag
- PU (SPU): 1 pcs
Connection data
- Connection technology: Push-in CAGE CLAMP®
- Fine-stranded conductor: 0.2 … 2.5 mm² / 24 … 12 AWG
- Solid conductor: 0.2 … 2.5 mm² / 24 … 12 AWG
- Strip length: 9 … 10 mm / 0.35 … 0.39 inches
- WAGO connector: picoMAX® 5.0
Environmental Product Compliance
- CAS-No.: 1303-86-2|1317-36-8|7439-92-1|75980-60-8|79-94-7
- REACH Candidate List Substance: 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol|Diboron trioxide|Lead|Lead monoxide|Perfluorobutane sulfonic acid (PFBS) and its salts|Phosphine oxide, diphenyl(2,4,6-trimethylbenzoyl)-
- RoHS Compliance Status: Compliant,With Exemption
- RoHS Exemption: 6(c)|7(a)|7(c)-I|7(c)-II
- SCIP notification number (Austria): 601bb33b-84cc-4805-b720-81f12c38c72c
- SCIP notification number (Belgium): 131209b7-ac71-4ce7-9b2f-c117badec519
- SCIP notification number (Bulgaria): 7c391072-6a84-41c0-a488-1eed30619da2
- SCIP notification number (Czech Republic): d1772c11-7a5d-49f4-8bb4-425bbedd445f
- SCIP notification number (Denmark): cfa32983-cc33-4189-b84e-a8b7c38e9bcd
- SCIP notification number (Finland): 5a251d21-3cd4-4150-8b9a-2dbe4ec1814c
- SCIP notification number (France): d428f471-7411-4cc1-9954-e2e708d38bac
- SCIP notification number (Germany): b09e21e7-8662-4ee1-ac5a-dcad6c89462f
- SCIP notification number (Hungary): 38a2a8e6-be31-466e-a297-d4ed34448198
- SCIP notification number (Italy): 76a372f1-e64e-48fc-aa2a-513cbdd7d1f7
- SCIP notification number (Netherlands): c7fe09a0-961d-444e-bccb-b777383080e3
- SCIP notification number (Poland): ef7bea4e-4cc5-4c67-a93e-8f9ee40db738
- SCIP notification number (Romania): 2fa777e0-ce5b-4d0f-9b8d-8e5b77843923
- SCIP notification number (Sweden): 6bc78593-b9a6-44e7-b529-4a5eada11443
Environmental requirements
- Ambient temperature (operation): -40 … +70 °C
- Ambient temperature (storage): -40 … +85 °C
- Temperature range of connection cable: ≥ (Tambient + 10 K)
- Temperature range of connection cable (UL): 80°C
Material data
- Fire load: 1.573MJ
- Weight: 63.9g
Mechanical data
- Mounting type: DIN-35 rail
Notes
- Note: This product is supplied with 24 VDC, which can be commoned using lateral push-in type jumper bars: (6.1) US+ (BR) and (6.2) GND 2 (BR). With this variant, it is necessary to ensure that the maximum permissible total current of 6 A is not exceeded.|Additional setting options via the WAGO Interface Configuration Software|This product is supplied with 24 VDC, which can be commoned using lateral push-in type jumper bars: (6.1) US+ (BR) and (6.2) GND 2 (BR). With this variant, it is necessary to ensure that the maximum permissible total current of 6 A is not exceeded.|Additional setting options via WAGO Interface Configuration Software or WAGO Interface Configuration App
Physical data
- Depth from upper-edge of DIN-rail: 107 mm / 4.213 inches
- Height: 110 mm / 4.331 inches
- Width: 12.5 mm / 0.492 inches
Safety and protection
- Insulation coordination (UL) - Insulation type (input, supply and service interface/relay output): Reinforced insulation (safe isolation)
- Insulation coordination (UL) - Insulation type (input/supply/service interface): Basic insulation
- Insulation coordination (UL) - Overvoltage category: II
- Insulation coordination (UL) - Pollution degree: 2
- Measurement category per EN/UL 61010-2-030: CAT II (input)
- Note on insulation parameters: Temperature sensors are not intended for use in dangerous circuits, provided the external temperature sensors used do not have basic insulation in accordance with EN/UL 61010-1 (300 VAC; overvoltage category II; pollution degree 2). The digital output (DO) is at the potential of the supply.|Temperature sensors are not intended for use in dangerous circuits, provided the external temperature sensors used do not have basic insulation in accordance with EN/UL 61010-1 (300 VAC; overvoltage category II; pollution degree 2).|The digital output (DO) is at the potential of the supply.
- Protection type: IP20
- Rated voltage: 300V
- Rated voltage of the measurement circuit connections per EN 61010-2-030: AC 300 V
- Test voltage - Test voltage (input/relay output/supply): 4 kVAC; 60 Hz; 1 min
- Test voltage - Test voltage (input/service interface): 3 kVAC; 60 Hz; 1 min
- Test voltage - Test voltage (relay output/service interface): 4 kVAC; 60 Hz; 1 min
- Test voltage - Test voltage (supply/service interface): 2.5 kVAC; 60 Hz; 1 min
Standards and specifications
- Conformity marking: CE
- EMC emission of interference: EN 61000-6-4; EN 61326-2-3; EN 50121-3-2
- EMC immunity to interference: EN 61000-6-2; EN 61326-2-3; EN 50121-3-2
- Standards/specifications: EN 61010-1|EN 61373|EN 50121-3-2|EN 50121-3-2|EN 61010-1|EN 61373
Technical data
- Configuration - Configuration options: WAGO Configuration Display|DIP switch|WAGO Interface Configuration Software|WAGO Interface Configuration App|WAGO Configuration Display
- Input - Input signal type: TC sensors
- Input (TC sensors) - Cold junction compensation: On/Off (Default: On)
- Input (TC sensors) - Cold junction error: 3 K (typ. 2 K )
- Input (TC sensors) - Sensor types (TC): Type J|Type K|Type E|Type N|Type R|Type S|Type T|Type B|Type C
- Input (TC sensors) - Temperature measurement range (TC): -210 … 1200 °C (Type J)|-200 … 1372 °C (Type K)
- Measurement error - Temperature coefficient: ≤ 0.01 %/K
- Measurement error - Transmission error (max.): ± 1 K
- Operating data - Continuous current (max.): 6 A
- Output (digital) - Configurable rise/fall delay time (DO): 0 … 60 s (via software)
- Output (digital) - Continuous current (DO) max.: 100 mA (no internal restriction)
- Output (digital) - Number of switching thresholds (DO): 1 or 2 (adjustable)
- Output (digital) - Switching voltage (DO) max.: Supply voltage (applied) - 0.3 V
- Output (relay) - Bounce time (typ.): 8ms
- Output (relay) - Configurable rise/fall delay time (relay): 0 … 60 s (via software)
- Output (relay) - Contact material (relay): AgNi + Au
- Output (relay) - Dielectric strength (open contact) (AC, 1 min): 1kVrms|1 kVrms
- Output (relay) - Drop-out time (typ.): 4ms
- Output (relay) - Number of changeover/switchover contacts: 1
- Output (relay) - Number of switching thresholds (relay): 1 or 2 (adjustable)
- Output (relay) - Pull-in time (typ.): 8ms
- Output (relay) - Switching Voltage, Max.: 250 VAC
- Power supply - Current consumption at nominal supply voltage: ≤ 40 mA (+ IDO)
- Power supply - Nominal supply voltage US: 24 VDC
- Power supply - Power supply type: 24 VDC
- Power supply - Supply voltage range: ±30 %
- Signal processing - Hysteresis: Adjustable via DIP switch or software
- Signal processing - Software filter (adjustable): Moving average value (filter level: 30)
- Signal processing - Step response (typ.): 60 ms (cold junction compensation Off)|360 ms (cold junction compensation On)