AC-to-DC or DC-to-DC switch-mode power supply unit (SMPS PSU) - WAGO (787 series) - 24Vdc / 4A / 96W output - Input voltage 90-265Vac (110Vac / 120Vac / 220Vac / 230Vac / 240Vac)/90-265Vdc (Single-phase AC (1AC) or DC) - with 3-pin 7/8" male connector (input) + 5-pin 7/8" female connector (output) - Wall (screws) mounting - IP67 - rated for -40°C...+85°C ambient - equivalent to 7876716

Specifications

  • Primary brand: WAGO
  • Network frequency: 47-63.6Hz
  • Functions: AC-to-DC or DC-to-DC switch-mode power supply unit (SMPS PSU)|Series operation possible (Max. 2 devices)|Parallel operation possible (Max. 3 devices)
  • Supply voltage (AC): 90-265Vac (110Vac / 120Vac / 220Vac / 230Vac / 240Vac)
  • Supply voltage (DC): 90-265Vdc
  • Display: LED status indication (DC OK -- green; Overload -- red)
  • Type of network: Single-phase AC (1AC) or DC
  • Rated current: 4A|6A (5s) PowerBoost (without voltage drop)
  • Rated power: 96W
  • Output voltage (DC): 24Vdc|23.52-24.48Vdc
  • Hold time: 45ms
  • Connection type: 3-pin 7/8" male connector (input)|5-pin 7/8" female connector (output)
  • Protection functions: T 6.3A internal fuse|Constant current|Short-circuit protection|Open circuit protection
  • Efficiency: 0.923
  • Mounting mode: Wall (screws)
  • Dimensions: H141mm x W111mm x D54mm
  • Ambient air temperature for operation: -40°C...+85°C
  • Ambient air temperature for storage: -40°C...+85°C
  • Humidity: 4-100% relative humidity (RH)
  • Current consumption: 0.5A (250Vac)|1.1A (100Vac)|9A inrush
  • GTIN code: 4055143644877
  • Customs Tariff Number: 85044083900
  • eClass code: 27-04-07-01
  • ETIM code: EC002540
  • Order code / Manufacturer SKU: 787-6716
  • Manufacturer product status: Commercialized
  • Equivalent to: 7876716
  • EAN code: 4055143644877
  • Compliant with standard(s): CE|EN 61010-1|EN 61010-2-201|EN 61204|UL 508|General approvals|- EAC - GZO Almaty Standart - TP TC 004/2011 - certificate EAC CoC 03078|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03081|- UL - Underwriters Laboratories Inc. - UL 508 - certificate E255817|Declarations of conformity and manufacturer's declarations|- EU-Declaration of Conformity - WAGO GmbH & Co. KG|RoHS compliant
  • Location of origin: Czech Republic
  • Ripple: 100mVpp (output voltage)|20mV (RMS)
  • MTBF (Mean Time Between Failures): 960 000h
  • Level 1 category: Automation components
  • Level 2 category: Power supply units
  • Product title: AC-to-DC or DC-to-DC switch-mode power supply unit (SMPS PSU) - WAGO

Commercial data

  • Country of origin: CZ
  • Customs tariff number: 85044083900
  • ECCN: NO US CLASSIFICATION
  • eCl@ss 10.0: 27-04-07-01
  • eCl@ss 9.0: 27-04-07-01
  • ETIM 8.0: EC002540
  • ETIM 9.0: EC002540
  • GTIN: 4055143644877
  • Packaging type: box
  • PU (SPU): 1 pcs

Connection data

  • Connection technology: 7/8"; 3-pole plug|7/8"; 5-pole socket
  • Connection type: Output
  • Connection type 1: Input

Environmental Product Compliance

  • RoHS Compliance Status: Compliant,No Exemption

Environmental requirements

  • Ambient temperature (operation): -40 … +85 °C
  • Ambient temperature (storage): -40 … +85 °C
  • Climatic category: 4K6 (per EN 60721)
  • Derating: -3.84 W/K (> 60 °C)
  • Relative humidity: 4 … 100 %

Material data

  • Weight: 1100g

Mechanical data

  • Mounting type: Screw mount

Physical data

  • Depth: 54 mm / 2.123 inches
  • Height: 141 mm / 5.55 inches
  • Width: 111 mm / 4.37 inches

Safety and protection

  • MTBF: > 960,000 h
  • Open-circuit-proof: Yes
  • Overvoltage protection; secondary: ≤ 30 VDC (per IEC 61131)
  • Parallel operation: 3 devices (max.)
  • Protection class: I
  • Protection type: IP67
  • Resistance to reverse feed: ≤ 35 VDC
  • Series operation: 2 devices (max.)
  • Short-circuit-protected: Yes

Standards and specifications

  • Conformity marking: CE
  • Standards/specifications: EN 61010-1|EN 61010-2-201|EN 61204|UL 508

Technical data

  • Circuit protection - Backup fusing (recommended): Circuit breaker: 4 … 20 A; Characteristic: C|T 20 A in building installations
  • Circuit protection - Internal fuse: T 6.3 A
  • Efficiency/power losses - Efficiency (typ.): 92.3 % (230 VAC)
  • Efficiency/power losses - Power loss Pl: ≤ 1 W; ≤ 7.9 W (nominal load)
  • Input - Input current Ii: ≤ 0.5 A (250 VAC); ≤ 1.1 A (100 VAC)
  • Input - Input voltage range: 90 … 265 VAC/VDC
  • Input - Inrush current: ≤ 9 A
  • Input - Mains failure hold-up time: ≥ 45 ms
  • Input - Nominal input voltage Ui nom: 100 … 240 VAC/VDC|AC/DC 100 … 240 V
  • Input - Nominal mains frequency range: 47 … 63.6 Hz; 0 Hz
  • Input - Phases: 1
  • Input - Power factor: ≥ 0.98
  • Input - Power factor correction (PFC): Active
  • Output - Nominal output current Io nom: 4 A
  • Output - Nominal output power: 96W
  • Output - Nominal output voltage Uo nom: 24 VDC
  • Output - Output voltage range: ±2 %
  • Output - Overload behavior: Constant current
  • Output - PowerBoost: DC 6 A (5 s; without voltage drop)
  • Output - Residual ripple: ≤ 100 mV (peak-to-peak); ≤ 20 mV (rms)
  • Signaling and communication - Operation status indicator: Green LED (24 VDC OK)|Red LED (overload)
  • Signaling and communication - Signaling: 1 x LED DC OK (green)|1 x Overload LED (red)