Wago - 750-838
$855.20
Sale price
$855.20
Regular price
Programmable Logic Controller (PLC) CPU unit - WAGO (750 series) - Controller CANopen; M1; D-Sub - 16-bit processor - 64 x connections per node + 110 x fieldbus mode on the controller (master) connection capability - with CANopen communication capability - supply voltage 18-31.2Vdc via wiring (24Vdc nom.) - with 9-pin D-sub connector (fieldbus) - DIN-35 rail mounting (71.1mm width) - IP20 - rated for 0°C...+55°C ambient - equivalent to 750838
Specifications
- Primary brand: WAGO
- Functions: Programmable Logic Controller (PLC) CPU unit|Configuration options|- EDS device description file|- WAGO-I/O-CHECK
- Supply voltage (DC): 18-31.2Vdc via wiring (24Vdc nom.)|18-31.2Vdc adjustable suppl. to field sensing devices
- Display: LED (STOP) red -- Device/node Stop|LED (RUN) green -- Initialization|LED (TX / RX OVERFLOW) red -- CAN send/receive buffer overflow|LED (I/O; USR) red/green/orange -- Local status / status programmable by user|LED (A; B) green -- Status of system power supply / field supply
- Processor type: 16-bit processor
- Programming languages: Instruction List (IL)|Ladder Diagram (LD)|Function Block Diagram (FBD)|Continuous Function Chart (CFC)|Structured Text (ST)|Sequential Function Chart (SFC)|Programming environment|- WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
- Memory capacity: 8kB non-volatile memory (software)|128kB (program memory)|64kB (data memory)|512bytes (fieldbus input and output memory)
- Connection capacity: 64 x connections per node|110 x fieldbus mode on the controller (master)
- Connection type: 9-pin D-sub connector (fieldbus)|CAGE CLAMP 2-pin (system supply)|CAGE CLAMP 6-pin (field supply)
- Mounting mode: DIN-35 rail
- Speed: 10kbit/s-1Mbit/s
- Dimensions: H100mm x W50.5mm x D71.1mm
- Net Width (mm): 71.1mm
- Material: Polycarbonate (PC) / Polyamide (PA) 6.6 housing
- Ambient air temperature for operation: 0°C...+55°C
- Ambient air temperature for storage: -25°C...+85°C
- Humidity: 95% relative humidity (RH; non-condensing)
- Mechanical resistance: Vibration resistance according to EN 60068-2-6 -- 4g|Shock resistance according to EN 60068-2-27 --15g
- Current consumption: 500mA (24Vdc; at nominal load)|350mA (5Vdc; system supply)|1650mA (system supply)
- Customs Tariff Number: 85371091990
- ETIM code: EC000236
- GTIN code: 4045454527136
- eClass code: 27-24-26-07
- Order code / Manufacturer SKU: 750-838
- Manufacturer product status: Commercialized
- Equivalent to: 750838
- EAN code: 4045454527136
- Compliant with standard(s): CE|EMC immunity to interference|- EN 61000-6-2|- marine applications|EMC emission of interference|- EN 61000-6-4|- marine applications|General approvals|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03083|- KC - National Radio Research Agency - Article 58-2 / Clause 3 - certificate MSIP-REM-W43-PFC750|- UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 508 - certificate E175199|Declarations of conformity and manufacturer's declarations|- EU-Declaration of Conformity - WAGO GmbH & Co. KG|Approvals for marine applications|- ABS - American Bureau of Shipping - certificate 22-2219060|- BSH - Bundesamt fuer Seeschifffahrt und Hydrographie - certificate 1104|- BV - Bureau Veritas S.A. - certificate 30389/C0 BV|- DNV - DNV GL SE - DNV-CG-0339 / Aug.2021 - certificate TAA0000194|- LR - Lloyds Register EMEA - certificate LR22180952TA|- PRS - Polski Rejestr Statkow - certificate TE/1101/880590/23|- RINA - RINA Germany GmbH - certificate ELE343521XG001|Approvals for hazardous areas|- ATEX - TUV Nord Cert GmbH - EN 60079-0 - certificate TUV14ATEX148929X (II 3 G Ex ec IIC T4 Gc)|- CCCEx - CQST/CNEx - CNCA-C23-01 - certificate 2020312310000213 (Ex ec IIC T4 Gc)|- IECEx - TUV Nord Cert GmbH - IEC 60079-0 - certificate IECEx TUN 14.0035 X (Ex ec IIC T4 Gc)|- INMETRO - TUV Rheinland do Brasil Ltda. - IEC 60079-0 - certificate TUV 12.1297 X|- UKEx - WAGO GmbH & Co. KG - EN 60079-0 - certificate UKCA_WAGO22UKEX003X_ec|- UL - Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS) - UL 121201 - certificate E198726|RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
- Location of origin: Germany
- Degree of pollution: 2
- Level 1 category: Automation components
- Level 2 category: Programmable Logic Controllers & components
- Level 3 category: CPU Units
- Product title: Programmable Logic Controller (PLC) CPU unit - WAGO (750 series)
Commercial data
- Country of origin: DE
- Customs tariff number: 85371091990
- ECCN: NO US CLASSIFICATION
- eCl@ss 10.0: 27-24-26-07
- eCl@ss 9.0: 27-24-26-07
- ETIM 8.0: EC000236
- ETIM 9.0: EC000236
- GTIN: 4045454527136
- Packaging type: box
- Product Group: 15 (I/O System)
- PU (SPU): 1 pcs
Connection data
- Connectable conductor materials: Copper
- Connection technology: communication/fieldbus: CANopen: 1 x D-sub 9 plug
- Connection technology: device configuration: 1 x Male connector; 4-pole
- Connection technology: field supply: 6 x CAGE CLAMP®
- Connection technology: system supply: 2 x CAGE CLAMP®
- Connection type 1: System/field supply
- Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Strip length: 8 … 9 mm / 0.31 … 0.35 inches
Environmental Product Compliance
- CAS-No.: 12060-00-3|1303-86-2|1317-36-8|25550-51-0|7439-92-1|79-94-7
- REACH Candidate List Substance: 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol|4-Methyl-1,2-cyclohexanedicarboxylic anhydride|Diboron trioxide|Lead|Lead monoxide|Lead titanium oxide (PbTiO3)
- RoHS Compliance Status: Compliant,With Exemption
- RoHS Exemption: 6(c)|7(a)|7(c)-I|7(c)-II
- SCIP notification number (Bulgaria): 666edaf8-99bf-435c-8e6d-f4bcd1cd8530
- SCIP notification number (Czech Republic): d8d702d0-b2bf-4ddc-9561-e78038776c2b
Environmental requirements
- Ambient temperature (operation): 0 … +55 °C
- Ambient temperature (storage): -25 … +85 °C
- EMC emission of interference: per EN 61000-6-4, marine applications
- EMC immunity to interference: per EN 61000-6-2, marine applications
- Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
- Fire load: 3.146MJ
- Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
- Mounting type: DIN-35 rail
- Operating altitude: without temperature derating: 0 … 2000 m; with temperature derating: 2000 … 5000 m (0.5 K/100 m); 5000 m (max.)
-
Permissible H2S contaminant concentration at a relative humidity
75 %: 10ppm -
Permissible SO2 contaminant concentration at a relative humidity
75 %: 25ppm - Pollution degree: 2 per IEC 61131-2
- Protection type: IP20
- Relative humidity (without condensation): 95%
- Shock resistance: 15g per IEC 60068-2-27
- Vibration resistance: 4g per IEC 60068-2-6
Mechanical data
- Color: light gray
- Conformity marking: CE
- Housing material: Polycarbonate; polyamide 6.6
- Weight: 184.2g
Notes
-
Note:
Note: Configuration files required (EDS)!
The EDS files can be downloaded for free at www.wago.com.
Physical data
- Depth: 71.1 mm / 2.799 inches
- Depth from upper-edge of DIN-rail: 63.9 mm / 2.516 inches
- Height: 100 mm / 3.937 inches
- Width: 50.5 mm / 1.988 inches
Technical data
- Bus segment length (max.): 1000 m
- COB ID distribution: SDO, standard
- Communications: CANopen
- Configuration options: EDS device description file|WAGO-I/O-CHECK
- CPU: 16 bits
- Current carrying capacity (power jumper contacts): 10A
- Current consumption (5 V system supply): 350mA
- Cycle time: < 3 ms for 1000 bit instructions/ 256 digital I/O
- Data memory: 64 KB
- Indicators: LED (STOP) red: Device/node Stop; LED (RUN) green: Initialization; LED (TX, RX OVERFLOW) red: CAN send/receive buffer overflow; LED (I/O, USR) red/green/orange: Local status, status programmable by user; LED (A, B) green: System power supply status, field supply
- Input and output process image (fieldbus) max.: 512 bytes/512 bytes
- Input current (typ.) at nominal load (24 V): 500mA
- Isolation: 500 V system/field
- Memory for fieldbus input variables (max.): 512Byte
- Memory for fieldbus output variables (max.): 512Byte
- Node ID distribution: DIP switch
- Non-volatile software memory: 8Kbytes
- Number of fieldbus nodes on master (max.): 110
- Number of modules per node (max.): 64
- Number of modules without a bus extension (max.): 64
- Number of outgoing power jumper contacts: 3
- Number of PDOs: 32 Tx / 32 Rx
- Number of SDOs: 2 SDO servers / 16 SDO clients
- Other CANopen features: NMT slave|Minimum boot-up|Variable PDO mapping|Emergency message|Life guarding/heartbeat|Empty module configuration
- Power supply efficiency (typ.) at nominal load (24 V): 87%
- Program memory: 128 KB
- Programming environment: WAGO-I/O-PRO V2.3 (based on CODESYS V2.3)
- Programming languages per IEC 61131-3: Instruction List (IL)|Ladder Diagram (LD)|Function Block Diagram (FBD)|Continuous Function Chart (CFC)|Structured Text (ST)|Sequential Function Chart (SFC)
- Supply voltage (field): 24 VDC (-25 … +30 %); via power jumper contacts
- Supply voltage (system): 24 VDC (-25 … +30 %); via pluggable connector (CAGE CLAMP® connection)
- Supported profiles: Communication profile: DS-301 V4.01; device profile: DS-401 V2.0; limit monitoring, flank-triggered PDOs, configurable response in the event of an error, DSP 405, NMT master programmable using function blocks
- Total current (system supply): 1,650mA
- Transmission medium (communication/fieldbus): Shielded Cu cable 3 x 0.25 mm²
- Transmission rate: 10 kBd … 1 MBd
- Visualization: none