Wago - 750-670
$496.20
Sale price
$496.20
Regular price
Stepper mtr. controller with 18-32.5Vdc adjustable suppl. to field sensing devices - WAGO (750 series) - Stepper Controller; RS-422/24Vdc; 20mA - with RS-422 communication capability - supply voltage 5Vdc (supplied by system) - with Push-in spring CAGE CLAMP connections - DIN-35 rail mounting (12mm width) - IP20 - rated for 0°C...+55°C ambient - equivalent to 750670
Specifications
- Primary brand: WAGO
- Functions: Stepper mtr. controller
- Design: 18-32.5Vdc adjustable suppl. to field sensing devices
- Supply voltage (DC): 5Vdc (supplied by system)|18-31.2Vdc adjustable suppl. to field sensing devices
- Display: LED (A-C/G) green -- Input 1 / Input 2 / Power Supply / Enable|LED (E/F) yellow -- Run / Run Program Active|LED (H) red -- Error
- Connection type: Push-in spring CAGE CLAMP connections
- Protection functions: short-circuit protection
- Mounting mode: DIN-35 rail
- Digital inputs: 2 x digital inputs (24Vdc transistor)|Digital inputs voltage ranges -3...+5Vdc (OFF) / 15-30Vdc (ON)
- Digital outputs: 2 x digital outputs (A1 / A2 / B1 / B2 encod. differential output)
- Dimensions: H100mm x W12mm x D67.8mm
- Net Width (mm): 12mm
- Material: Polycarbonate (PC) / Polyamide (PA) 6.6 housing
- Ambient air temperature for operation: 0°C...+55°C
- Ambient air temperature for storage: -40°C...+85°C
- Humidity: 95% relative humidity (RH; non-condensing)
- Mechanical resistance: Shock resistance according to EN 60068-2-27 --15g
- Current consumption: 98mA (5Vdc; system supply)
- ETIM code: EC001601
- eClass code: 27-24-26-05
- Customs Tariff Number: 85389099990
- GTIN code: 4045454539719
- Order code / Manufacturer SKU: 750-670
- Manufacturer product status: Commercialized
- Equivalent to: 750670
- EAN code: 4045454539719
- Compliant with standard(s): CE|EMC immunity to interference|- EN 61000-6-2|EMC emission of interference|- EN 61000-6-3|General approvals|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03083|- KC - National Radio Research Agency - Article 58-2 / Clause 3 - certificate MSIP-REM-W43-MCM750|- UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 508 - certificate E175199|Declarations of conformity and manufacturer's declarations|- EU-Declaration of Conformity - WAGO GmbH & Co. KG|Approvals for hazardous areas|- ATEX - TUV Nord Cert GmbH - EN 60079-0 - certificate TUV14ATEX148929X (II 3 G Ex ec IIC T4 Gc)|- CCCEx - CQST/CNEx - CNCA-C23-01 - certificate 2020312310000213 (Ex ec IIC T4 Gc)|- IECEx - TUV Nord Cert GmbH - IEC 60079-0 - certificate IECEx TUN 14.0035 X (Ex ec IIC T4 Gc)|- INMETRO - TUV Rheinland do Brasil Ltda. - IEC 60079-0 - certificate TUV 12.1297 X|- UKEx - WAGO GmbH & Co. KG - EN 60079-0 - certificate UKCA_WAGO22UKEX003X_ec|- UL - Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS) - UL 121201 - certificate E198726|RoHS compliant
- Location of origin: Germany
- Degree of pollution: 2
- Level 1 category: Automation components
- Level 2 category: Motor & motion control
- Level 3 category: Motion control (Servo motors and Drives)
- Level 4 category: Stepper motor controllers
- Product title: Stepper mtr. controller - WAGO
Commercial data
- Country of origin: DE
- Customs tariff number: 85389099990
- ECCN: NO US CLASSIFICATION
- eCl@ss 10.0: 27-24-26-05
- eCl@ss 9.0: 27-24-26-05
- ETIM 8.0: EC001601
- ETIM 9.0: EC001601
- GTIN: 4045454539719
- Packaging type: box
- Product Group: 15 (I/O System)
- PU (SPU): 1 pcs
Connection data
- Connectable conductor materials: Copper
- Connection technology: inputs/outputs: 8 x CAGE CLAMP®
- Connection type 1: Inputs/Outputs
- Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Strip length: 8 … 9 mm / 0.31 … 0.35 inches
Environmental Product Compliance
- RoHS Compliance Status: Compliant,No Exemption
Environmental requirements
- Ambient temperature (operation): 0 … +55 °C
- Ambient temperature (storage): -40 … +85 °C
- EMC emission of interference: per EN 61000-6-3
- EMC immunity to interference: per EN 61000-6-2
- Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
- Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
- Operating altitude: 0 … 2000 m / 0 … 6562 ft
-
Permissible H2S contaminant concentration at a relative humidity
75 %: 10ppm -
Permissible SO2 contaminant concentration at a relative humidity
75 %: 25ppm - Pollution degree: 2 per IEC 61131-2
- Protection type: IP20
- Relative humidity (without condensation): 95%
- Shock resistance: 15g per IEC 60068-2-27
- Vibration resistance: per IEC 60068-2-6
Material data
- Color: light gray
- Conformity marking: CE
- Fire load: 1.136MJ
- Housing material: Polycarbonate; polyamide 6.6
- Weight: 49.9g
Mechanical data
- Mounting type: DIN-35 rail
Physical data
- Depth: 67.8 mm / 2.669 inches
- Depth from upper-edge of DIN-rail: 60.6 mm / 2.386 inches
- Height: 100 mm / 3.937 inches
- Width: 12 mm / 0.472 inches
Technical data
- Current consumption (5 V system supply): 98mA
- Data width: 12-byte input/output
- Device-specific: Operating modes: Individual positioning, reference run, jog, tip, command tables, PWM
- Duty cycle: 50 % (in stepper motor mode)
- Functions: Absolute/relative positioning, setpoint change on the fly, rotary axis, etc.
- Indicators: LED (A-C, G) green: Input 1, Input 2, Power Supply, Enable; LED (E, F) yellow: Run, Run Program Active; LED (H) red: Error
- Input current (typ.): 2.8 mA
- Input filter: 100 µs, software filter can be connected
- Isolation: 500 V system/field
- Load type: RS-422, TTL, optocoupler
- Number of digital inputs: 2
- Number of incoming power jumper contacts: 2
- Number of outgoing power jumper contacts: 2
- Number of outputs: 1 channel (2 differential outputs A1, A2, B1, B2)
- Output current: short-circuit-protected
- Output current per channel: 0.03A
- Resolution: 15 bits + 16 bit prescaler
- Signal frequency (max.): 500000Hz
- Signal frequency (min.): 0Hz
- Signal voltage: 5 VDC (internal), 5 … 24 VDC (external)
- Stepper resolution: 23 bits + sign bit
- Supply voltage (field): 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
- Supply voltage (system): 5 VDC; via data contacts
- Voltage range for signal (0): −3 … +5 VDC
- Voltage range for signal (1): 15 … 30 VDC