Fail-safe / safety DC digital input/output slice unit module - Safety Cat2/SIL2 or Cat4/SIL3 - WAGO (750 series) - 4FDI/4FDO; 24Vdc; 0.5A; PROFIsafe - 8I/O [4DI (4 x digital inputs (fail-safe inputs with test pulse; clock sensitive; 24Vdc)) + 4DO (4 x digital outputs (fail-safe outputs with test pulse / 24Vdc per channel))] - with PROFIsafe communication capability - supply voltage 5Vdc (supplied by system) - with spring CAGE CLAMP connections - DIN-35 rail mounting (24mm width) - IP20 - rated for 0°C...+55°C ambient - equivalent to 750665000001

Specifications

  • Primary brand: WAGO
  • Functions: Fail-safe / safety DC digital input/output slice unit module|Configuration options|- PROFIsafe address adjustable via DIP switch or engineering software
  • Supply voltage (DC): 5Vdc (supplied by system)|20.4-28.8Vdc adjustable suppl. to field sensing devices
  • Frequency: 5Hz switching frequency
  • Display: LED (A-H) green -- Status I1...I8|LED (I-K) red -- internal/external error
  • Connection type: spring CAGE CLAMP connections
  • Mounting mode: DIN-35 rail
  • Digital inputs: 4 x digital inputs (fail-safe inputs with test pulse; clock sensitive; 24Vdc)
  • Digital outputs: 4 x digital outputs (fail-safe outputs with test pulse / 24Vdc per channel)
  • Dimensions: H100mm x W24mm x D67.8mm
  • Net Width (mm): 24mm
  • Material: Polycarbonate (PC) / Polyamide (PA) 6.6 housing
  • Ambient air temperature for operation: 0°C...+55°C
  • Ambient air temperature for storage: -25°C...+85°C
  • Humidity: 95% relative humidity (RH; non-condensing)
  • Mechanical resistance: Shock resistance according to EN 60068-2-27 --15g
  • Current consumption: 55mA (5Vdc; system supply)
  • GTIN code: 4045454767952
  • ETIM code: EC001599
  • eClass code: 27-24-26-04
  • Customs Tariff Number: 85371098990
  • Order code / Manufacturer SKU: 750-665/000-001
  • Manufacturer product status: Commercialized
  • Equivalent to: 750665000001
  • EAN code: 4045454767952
  • Compliant with standard(s): CE|EMC immunity to interference|- EN 61000-6-2|EMC emission of interference|- EN 61000-6-4|General approvals|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03083|- KC - National Radio Research Agency - Article 58-2 / Clause 3 - certificate MSIP-REM-W43-DI0750|- UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 508 - certificate E175199|Declarations of conformity and manufacturer's declarations|- EU-Declaration of Conformity - WAGO GmbH & Co. KG|- UK-Declaration of Conformity - WAGO GmbH & Co. KG|Approvals for hazardous areas|- ATEX - TUV Nord Cert GmbH - EN 60079-0 - certificate TUV14ATEX148929X (II 3 G Ex ec IIC T4 Gc)|- CCCEx - CQST/CNEx - CNCA-C23-01 - certificate 2020312310000213 (Ex ec IIC T4 Gc)|- IECEx - TUV Nord Cert GmbH - IEC 60079-0 - certificate IECEx TUN 14.0035 X (Ex ec IIC T4 Gc)|- INMETRO - TUV Rheinland do Brasil Ltda. - IEC 60079-0 - certificate TUV 12.1297 X|- UKEx - WAGO GmbH & Co. KG - EN 60079-0 - certificate UKCA_WAGO22UKEX003X_ec|- UL - Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS) - UL 121201 - certificate E198726|RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
  • Class: Safety Cat2/SIL2 or Cat4/SIL3
  • Location of origin: Germany
  • Degree of pollution: 2
  • Level 1 category: Safety components
  • Level 2 category: Safety I-O Units
  • Product title: Fail-safe / safety DC digital input/output slice unit module - WAGO

Commercial data

  • Country of origin: DE
  • Customs tariff number: 85371098990
  • ECCN: NO US CLASSIFICATION
  • eCl@ss 10.0: 27-24-26-04
  • eCl@ss 9.0: 27-24-26-04
  • ETIM 8.0: EC001599
  • ETIM 9.0: EC001599
  • GTIN: 4045454767952
  • Packaging type: Box
  • Product Group: 15 (I/O System)
  • PU (SPU): 1 pcs

Connection data

  • Connectable conductor materials: Copper
  • Connection technology: inputs/outputs: 16 x CAGE CLAMP®
  • Connection type 1: Inputs/outputs
  • Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Strip length: 8 … 9 mm / 0.31 … 0.35 inches

Digitale Ausgänge

  • Actuator connection: 4 x (fail-safe output with test pulse)
  • Number of digital outputs: 4
  • Output circuit design: Power outputs
  • Response times (max.) (outputs): ton (L->H) = 13 ms; toff (H->L) = 13 ms; plus 2 x local bus runtime; plus 2 x fieldbus runtime; plus PLC runtime
  • Signal type: Digital
  • Signal type (voltage): 24 VDC
  • Switching frequency (max.): 5 Hz; Resistive load
  • Switching frequency (max.) (2): 0.1 Hz; Inductive load per IEC 947-5-1, DC 13
  • Switching frequency (max.) (3): 5 Hz; Inductive load per IEC 947-5-1, DC 13; with recovery diodes

Digitale Eingänge

  • Input characteristic: clock sensitive
  • Input current per channel for signal (1) typ.: 2.2mA
  • Number of digital inputs: 4
  • Response times (min. … max.) (inputs): ton (L->H) = 13 ms … 71 ms; toff (H->L) = 13 ms … 26 ms; plus 2 x local bus runtime; plus 2 x fieldbus runtime; plus PLC runtime
  • Sensor connection: 4 x (Fail-safe input with test pulse)
  • Signal type: Digital
  • Signal type (voltage): 24 VDC

Digitale Taktausgänge

  • Signal type: Digital
  • Signal type (voltage): 24 VDC

Environmental Product Compliance

  • CAS-No.: 12060-00-3|1303-86-2|1317-36-8|7439-92-1
  • REACH Candidate List Substance: Diboron trioxide|Lead|Lead monoxide|Lead titanium oxide (PbTiO3)
  • RoHS Compliance Status: Compliant,With Exemption
  • RoHS Exemption: 6(c)|7(a)|7(c)-I|7(c)-II
  • SCIP notification number (Bulgaria): a7910311-1bf3-4f71-a861-c41c61c1d680
  • SCIP notification number (Czech Republic): d6e2d4d1-38e2-4067-bcb8-52d96ea4a33d

Environmental requirements

  • Ambient temperature (operation): 0 … +55 °C
  • Ambient temperature (storage): -25 … +85 °C
  • EMC emission of interference: per EN 61000-6-4
  • EMC immunity to interference: per EN 61000-6-2
  • Exposure to pollutants: per IEC 60068-2-42 and IEC 60068-2-43
  • Mounting position: Horizontal left, horizontal right, horizontal top, vertical top and vertical bottom
  • Operating altitude: 0 … 2000 m / 0 … 6562 ft
  • Permissible H2S contaminant concentration at a relative humidity 75 %: 10ppm
  • Permissible SO2 contaminant concentration at a relative humidity 75 %: 25ppm
  • Pollution degree: 2 per IEC 61131-2
  • Protection type: IP20
  • Relative humidity (without condensation): 95%
  • Shock resistance: 15g per IEC 60068-2-27
  • Vibration resistance: per IEC 60068-2-6

Functional Safety

  • Achievable safety classes: 4 x Cat. 2/SIL 2 or 2 x Cat. 4/SIL 3
  • Load reactances (max.): Capacitive 2 nF; inductive corresponding to DC 13
  • Proof test interval: 10years

General technical data

  • Configuration options: PROFIsafe address adjustable via DIP switch or engineering software
  • Indicators: LED (A-H) green: Status I1 … I8; LED (I-K) red: internal, external error
  • Protocols: PROFIsafe V1.3
  • Total number of channels (module): 8

Material data

  • Color: yellow
  • Conformity marking: CE
  • Fire load: 2.955MJ
  • Housing material: Polycarbonate; polyamide 6.6
  • Weight: 101.2g

Mechanical data

  • Mounting type: DIN-35 rail

Physical data

  • Depth: 67.8 mm / 2.669 inches
  • Depth from upper-edge of DIN-rail: 60.6 mm / 2.386 inches
  • Height: 100 mm / 3.937 inches
  • Width: 24 mm / 0.945 inches

Technical data

  • Current carrying capacity (power jumper contacts): 10A
  • Current consumption (5 V system supply): 55mA
  • Isolation: 500 V system/field
  • Number of incoming power jumper contacts: 2
  • Number of outgoing power jumper contacts: 2
  • Supply voltage (field): 24 VDC (-15 … +20 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
  • Supply voltage (system): 5 VDC; via data contacts