Standard analog input slice unit module - WAGO (750 series) - 2AI; 4-20mA; SE - 2I/O [2AI (2 x analog inputs (4-20mA; Single-ended; 12-bits / 80ms conversion; 2-wire / 3-wire))] - supply voltage 5Vdc (supplied by system) - with spring CAGE CLAMP connections - DIN-35 rail mounting (12mm width) - IP20 - rated for 0°C...+55°C ambient - equivalent to 750473

Specifications

  • Primary brand: WAGO
  • Functions: Standard analog input slice unit module
  • Supply voltage (DC): 5Vdc (supplied by system)|18-31.2Vdc adjustable suppl. to field sensing devices
  • Display: LED (A/C) green -- Function AI 1 / AI 2|LED (B/D) red -- Error AI 1 / AI 2
  • Connection type: spring CAGE CLAMP connections
  • Protection functions: short-circuit protection
  • Mounting mode: DIN-35 rail
  • Analog inputs: 2 x analog inputs (4-20mA; Single-ended; 12-bits / 80ms conversion; 2-wire / 3-wire)
  • Measurement accuracy: +-0.1% (measuring error)|+-0.01% (temperature error)
  • Dimensions: H100mm x W12mm x D69.8mm
  • Net Width (mm): 12mm
  • Material: Polycarbonate (PC) / Polyamide (PA) 6.6 housing
  • Ambient air temperature for operation: 0°C...+55°C
  • Ambient air temperature for storage: -40°C...+85°C
  • Humidity: 95% relative humidity (RH; non-condensing)
  • Mechanical resistance: Vibration resistance according to EN 60068-2-6 -- 4g|Shock resistance according to EN 60068-2-27 --15g
  • Current consumption: 100mA (5Vdc; system supply)
  • ETIM code: EC001596
  • GTIN code: 4050821867050
  • eClass code: 27-24-26-01
  • Customs Tariff Number: 85389099990
  • Order code / Manufacturer SKU: 750-473
  • Manufacturer product status: Commercialized
  • Equivalent to: 750473
  • EAN code: 4050821867050
  • Compliant with standard(s): CE|EMC immunity to interference|- EN 61000-6-2|- marine applications|EMC emission of interference|- EN 61000-6-3|- marine applications|General approvals|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03083|- KC - National Radio Research Agency - Article 58-2 / Clause 3 - certificate MSIP-REM-W43-AIM750|- UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 508 - certificate E175199|Declarations of conformity and manufacturer's declarations|- EU-Declaration of Conformity - WAGO GmbH & Co. KG|Approvals for marine applications|- ABS - American Bureau of Shipping - certificate 22-2219060|- BSH - Bundesamt fuer Seeschifffahrt und Hydrographie - certificate 1104|- BV - Bureau Veritas S.A. - certificate 13453/E0 BV|- DNV - DNV GL SE - DNV-CG-0339 / Aug.2021 - certificate TAA0000194|- KR - Korean Register of Shipping - certificate KR HMB05880-AC001|- LR - Lloyds Register EMEA - certificate LR22180952TA|- PRS - Polski Rejestr Statkow - certificate TE/1101/880590/23|- RINA - RINA Germany GmbH - certificate ELE343521XG001|Approvals for hazardous areas|- ATEX - TUV Nord Cert GmbH - EN 60079-0 - certificate TUV14ATEX148929X (II 3 G Ex ec IIC T4 Gc)|- CCCEx - CQST/CNEx - CNCA-C23-01 - certificate 2020312310000213 (Ex ec IIC T4 Gc)|- IECEx - TUV Nord Cert GmbH - IEC 60079-0 - certificate IECEx TUN 14.0035 X (Ex ec IIC T4 Gc)|- INMETRO - TUV Rheinland do Brasil Ltda. - IEC 60079-0 - certificate TUV 12.1297 X|- KTL - Korea Testing Laboratory - KOSHA Article 34 / IEC60079-0 - certificate 21-KA4BO-0550X|- UKEx - WAGO GmbH & Co. KG - EN 60079-0 - certificate UKCA_WAGO22UKEX003X_ec|- UL - Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS) - UL 121201 - certificate E198726|RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
  • Location of origin: Germany
  • Degree of pollution: 2
  • Level 1 category: Automation components
  • Level 2 category: Programmable Logic Controllers & components
  • Level 3 category: I-O Units
  • Product title: Standard analog input slice unit module - WAGO

Commercial data

  • Country of origin: DE
  • Customs tariff number: 85389099990
  • ECCN: NO US CLASSIFICATION
  • eCl@ss 10.0: 27-24-26-01
  • eCl@ss 9.0: 27-24-26-01
  • ETIM 8.0: EC001596
  • ETIM 9.0: EC001596
  • GTIN: 4050821867050
  • Packaging type: box
  • Product Group: 15 (I/O System)
  • PU (SPU): 1 pcs

Connection data

  • Connectable conductor materials: Copper
  • Connection technology: inputs/outputs: 8 x CAGE CLAMP®
  • Connection type 1: Inputs/Outputs
  • Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Strip length: 8 … 9 mm / 0.31 … 0.35 inches

Environmental Product Compliance

  • CAS-No.: 1303-86-2|1317-36-8|7439-92-1
  • REACH Candidate List Substance: Diboron trioxide|Lead|Lead monoxide
  • RoHS Compliance Status: Compliant,With Exemption
  • RoHS Exemption: 6(c)|7(a)|7(c)-I|7(c)-II
  • SCIP notification number (Austria): ef1c0287-e045-4bc7-83a4-56d4c5d9405a
  • SCIP notification number (Belgium): db80695c-b7e8-4867-bbfc-37c933bb3e2b
  • SCIP notification number (Bulgaria): efaef65e-45f6-471d-b41e-d4b69160d158
  • SCIP notification number (Czech Republic): 815ae1d9-6fd7-4abb-97fb-6e24540d51f4
  • SCIP notification number (Denmark): 24ec15d5-a1d7-4bba-95e8-93f96696a2c8
  • SCIP notification number (Finland): 0e56b0d4-8808-441f-a2bf-8ec5ca17948d
  • SCIP notification number (France): 3508a5c9-d93f-4e92-9e16-e0405508edf0
  • SCIP notification number (Germany): 05659525-a3c0-49af-a7c4-9e695e43c52c
  • SCIP notification number (Hungary): 5df1f6e6-58cb-46f6-9b2d-6b223e71f402
  • SCIP notification number (Italy): 9eafc3f1-0c2e-4cc8-a820-7c8d6bf6cee5
  • SCIP notification number (Netherlands): d11b8fb9-9442-4593-b266-d6b86410384a
  • SCIP notification number (Poland): cce945f9-d83c-481f-9804-2cb5bf64c7ae
  • SCIP notification number (Romania): acfe4b1e-bc30-43e0-8328-a9316b63d3fa
  • SCIP notification number (Sweden): d67bce5b-b93b-4bcd-a29e-7a1df41e6a20

Environmental requirements

  • Ambient temperature (operation): 0 … +55 °C
  • Ambient temperature (storage): -40 … +85 °C
  • EMC emission of interference: per EN 61000-6-3, marine applications
  • EMC immunity to interference: per EN 61000-6-2, marine applications
  • Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
  • Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
  • Operating altitude: 0 … 2000 m / 0 … 6562 ft
  • Permissible H2S contaminant concentration at a relative humidity 75 %: 10ppm
  • Permissible SO2 contaminant concentration at a relative humidity 75 %: 25ppm
  • Pollution degree: 2 per IEC 61131-2
  • Protection type: IP20
  • Relative humidity (without condensation): 95%
  • Shock resistance: 15g per IEC 60068-2-27
  • Vibration resistance: 4g per IEC 60068-2-6

Material data

  • Color: light gray
  • Conformity marking: CE
  • Fire load: 0.967MJ
  • Housing material: Polycarbonate; polyamide 6.6
  • Weight: 53g

Mechanical data

  • Mounting type: DIN-35 rail

Physical data

  • Depth: 69.8 mm / 2.748 inches
  • Depth from upper-edge of DIN-rail: 62.6 mm / 2.465 inches
  • Height: 100 mm / 3.937 inches
  • Width: 12 mm / 0.472 inches

Technical data

  • Conversion time (typ.): 80ms
  • Current consumption (5 V system supply): 100mA
  • Data width: 2 x 16-bit data; 2 x 8-bit control/status (optional)
  • Indicators: LED (A, C) green: Function AI 1, AI 2; LED (B, D) red: Error AI 1, AI 2
  • Input filter frequency (analog): 50Hz
  • Input resistance (max.): 160Ω
  • Input voltage (note): Non-linear, overload protected U = 1.2 V + 100 Ω x I meas
  • Isolation: 500 V system/field
  • Measurement error (reference temperature): 25°C
  • Measurement error, deviation (max.) from the upper-range value: 0.1%
  • Noise rejection above sampling frequency: -40dB
  • Noise rejection at sampling frequency: -100dB
  • Number of analog inputs: 2
  • Number of incoming power jumper contacts: 2
  • Number of outgoing power jumper contacts: 2
  • Resolution [bit]: 12bits
  • Sensor connection: 2 x (2-wire, 3-wire)
  • Signal characteristics: Single-ended
  • Signal type: Current
  • Signal type (current): 4 … 20 mADC
  • Supply voltage (field): 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
  • Supply voltage (system): 5 VDC; via data contacts
  • Temperature error (max.) of the upper-range value: 0.01%/K
  • Total number of channels (module): 2