Skip to product information
Wago - 750-486
$1,653.00
Sale price
$1,653.00
Regular price
Intrinsically-safe analog input slice unit module - WAGO (750 series) - 4AI; 0/4-20mA; NE43; Ex i - 4I/O [4AI (4 x analog inputs (0-20mA / 4-20mA; Single-ended; 12-bits / 10ms conversion; 2-wire))] - supply voltage 5Vdc (supplied by system) - with spring CAGE CLAMP connections - DIN-35 rail mounting (24mm width) - IP20 - rated for 0°C...+55°C ambient - equivalent to 750486
Specifications
- Primary brand: WAGO
- Functions: Intrinsically-safe analog input slice unit module
- Supply voltage (DC): 5Vdc (supplied by system)|24Vdc fixed suppl. to field sensing devices
- Display: LED (A/E/C/G) green -- Function AI 1...AI 4|LED (B/F/D/H) red -- Error AI 1...AI 4
- Connection type: spring CAGE CLAMP connections
- Mounting mode: DIN-35 rail
- Analog inputs: 4 x analog inputs (0-20mA / 4-20mA; Single-ended; 12-bits / 10ms conversion; 2-wire)
- Measurement accuracy: +-0.1% (measuring error)|+-0.01% (temperature error)
- Dimensions: H100mm x W24mm x D67.8mm
- Net Width (mm): 24mm
- Material: Polycarbonate (PC) / Polyamide (PA) 6.6 housing
- Ambient air temperature for operation: 0°C...+55°C
- Ambient air temperature for storage: -25°C...+85°C
- Humidity: 95% relative humidity (RH; non-condensing)
- Mechanical resistance: Shock resistance according to EN 60068-2-27 --15g
- Current consumption: 45mA (5Vdc; system supply)|19mA (field supply; no external load)
- Power consumption: 2.7W
- ETIM code: EC001596
- Customs Tariff Number: 85389099990
- eClass code: 27-24-26-01
- Power dissipation/losses: 1.5W
- Order code / Manufacturer SKU: 750-486
- Manufacturer product status: Commercialized
- Equivalent to: 750486
- EAN code: 4055143516044
- Compliant with standard(s): CE|EMC immunity to interference|- EN 61000-6-2|- marine applications|EMC emission of interference|- EN 61000-6-3|- marine applications|General approvals|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03083|- KC - National Radio Research Agency - Article 58-2 / Clause 3 - certificate MSIP-REM-W43-AIM750|- UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - certificate E175199|Declarations of conformity and manufacturer's declarations|- EU-Ex-Declaration of Conformity - WAGO GmbH & Co. KG|- UK-Ex-Declaration of Conformity - WAGO GmbH & Co. KG|Approvals for marine applications|- ABS - American Bureau of Shipping - certificate 22-2219060|- DNV - DNV GL SE - DNV-CG-0339 / Aug.2021 - certificate TAA0000194|- KR - Korean Register of Shipping - certificate KR HMB05880-AC001|- LR - Lloyds Register EMEA - certificate LR22180952TA|- PRS - Polski Rejestr Statkow - certificate TE/1101/880590/23|- RINA - RINA Germany GmbH - certificate ELE343521XG001|Approvals for hazardous areas|- ATEX - TUV Nord Cert GmbH - EN 60079-0 - certificate TUV12ATEX106032X (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)|- CCC - CNEX - CNCA-C23-01 - certificate 2020312310000211 (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)|- IECEx - TUV Nord Cert GmbH - IEC 60079 / IEC 60079-0 - certificate IECEx TUN12.0039X (Ex ec[iaGa] IIC T4 Gc / [Ex iaDa] IIIC / [Ex iaMa] I)|- INMETRO - TUV Rheinland do Brasil Ltda. - certificate TUV_14.1911_X|- KTL - Korea Testing Laboratory - KOSHA Article 34 / IEC60079-0 - certificate 20-KA4BO-0606X|- UKEx - Element Materials Technology UK - certificate EMA21UKEX0069X|- UL - Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS) - UL 121201 - certificate E198726|RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
- Location of origin: Germany
- Degree of pollution: 2
- Level 1 category: Automation components
- Level 2 category: Programmable Logic Controllers & components
- Level 3 category: I-O Units
- Product title: Intrinsically-safe analog input slice unit module - WAGO
Commercial data
- Country of origin: DE
- Customs tariff number: 85389099990
- ECCN: NO US CLASSIFICATION
- eCl@ss 10.0: 27-24-26-01
- eCl@ss 9.0: 27-24-26-01
- ETIM 8.0: EC001596
- ETIM 9.0: EC001596
- Packaging type: Box
- PU (SPU): 1 pcs
Connection data
- Connectable conductor materials: Copper
- Connection technology: inputs/outputs: 16 x CAGE CLAMP®
- Connection type 1: Inputs/outputs
- Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Strip length: 8 … 9 mm / 0.31 … 0.35 inches
Environmental Product Compliance
- CAS-No.: 1303-86-2|1317-36-8|7439-92-1
- REACH Candidate List Substance: Diboron trioxide|Lead|Lead monoxide
- RoHS Compliance Status: Compliant,With Exemption
- RoHS Exemption: 6(c)|7(a)|7(c)-I|7(c)-II
- SCIP notification number (Austria): 549055d6-6f9f-4c9d-b855-7486a1d6cb3a
- SCIP notification number (Belgium): 7c5e0ec5-4b5c-495e-85ab-8c4b17d0b137
- SCIP notification number (Bulgaria): 485c2c34-1cda-4cc4-a49f-bdbe01d8d580
- SCIP notification number (Czech Republic): 474cd881-197a-4e7f-9d9d-56ae52483311
- SCIP notification number (Denmark): 7f8cc8a2-4c17-4246-901a-f36a098de931
- SCIP notification number (Finland): 7602d62b-94b5-44a6-8da6-ccfea8ef5ecf
- SCIP notification number (France): 60a2160b-b980-4efb-ba16-b12cd1cabb0d
- SCIP notification number (Germany): 9e11c3b8-9702-4919-a91b-bda35f90810c
- SCIP notification number (Hungary): 8119bf7f-3b21-48b7-ab84-a594bf80a530
- SCIP notification number (Italy): 40b21ee0-9bc8-486f-9958-c6e22e9afb1b
- SCIP notification number (Netherlands): 97e4e9f6-cc3f-4289-9a68-d071c0e6fa99
- SCIP notification number (Poland): f0ea8734-9828-4e42-86bd-3c858df8aa95
- SCIP notification number (Romania): 8d08dea9-f978-4ce4-9dc1-dcf3e759b55f
- SCIP notification number (Sweden): c378fdab-274a-422c-a91c-1e8be031c67d
Environmental requirements
- Ambient temperature (operation): 0 … +55 °C
- Ambient temperature (storage): -25 … +85 °C
- EMC emission of interference: per EN 61000-6-3, marine applications
- EMC immunity to interference: per EN 61000-6-2, marine applications
- Exposure to pollutants: per IEC 60068-2-42 and IEC 60068-2-43
- Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
- Operating altitude: 0 … 2000 m / 0 … 6562 ft
-
Permissible H2S contaminant concentration at a relative humidity
75 %: 10ppm -
Permissible SO2 contaminant concentration at a relative humidity
75 %: 25ppm - Pollution degree: 2 per IEC 61131-2
- Protection type: IP20
- Relative humidity (without condensation): 95%
- Shock resistance: 15g per IEC 60068-2-27
- Vibration resistance: per IEC 60068-2-6
Explosion protection
- Ex standard: EN IEC 60079-0, -7, -11
-
Identification: ATEX
II 3 (1) G Ex ec [ia Ga] IIC T4 Gc
II (1) D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I|IECEx/ INMETRO
Ex ec [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
[Ex ia Ma] I - Reactances (note): Reactances without accounting for the concurrence of capacitance (Co) and inductance (Lo)
- Reactances Ex ia I: Lo = 31 mH; Co = 3.6 µF
- Reactances Ex ia IIA: Lo = 22 mH; Co = 2.28 μF
- Reactances Ex ia IIB: Lo = 13 mH; Co = 683 nF
- Reactances Ex ia IIC: Lo = 970 µH; Co = 88 nF
- Safety-relevant data (circuit): Uo = 27.3 V; Io = 98.4 mA; Po = 0.672 W; linear characteristic curve
Material data
- Color: blue
- Conformity marking: CE
- Fire load: 2.033MJ
- Housing material: Polycarbonate; polyamide 6.6
- Weight: 116g
Mechanical data
- Mounting type: DIN-35 rail
Notes
-
Note:
The analog input module must only be operated via 24 VDC Ex i!
General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals!
Physical data
- Depth: 67.8 mm / 2.669 inches
- Depth from upper-edge of DIN-rail: 60.6 mm / 2.386 inches
- Height: 100 mm / 3.937 inches
- Width: 24 mm / 0.945 inches
Technical data
- Conversion time (typ.): 10ms
- Current carrying capacity (power jumper contacts): 1A
- Current consumption (5 V system supply): 45mA
- Current consumption, field supply (module with no external load): 19mA
- Data width: 4 x 16-bit data; 4 x 8-bit control/status (optional)
- Indicators: LED (A, E, C, G) green: Function AI 1 … AI 4; LED (B, F, D, H) red: Error AI 1 … AI 4
- Input resistance (max.): 200Ω
- Intrinsically safe Ex i: Yes
- Isolation: UM = 375 V system/supply
- Item description: 4-Channel Analog Input; 0/4 … 20 mA; NAMUR NE43
- Measurement error (reference temperature): 25°C
- Measurement error, deviation (max.) from the upper-range value: ±0.1%
- Number of analog inputs: 4
- Number of incoming power jumper contacts: 2
- Number of outgoing power jumper contacts: 2
- Power consumption Pmax.: 2.7 W (at 4 x 21 mA signal current)
- Power loss Pl: 1.5 W (at 4 x 21 mA signal current)
- Resolution [bit]: 12bits
- Sensor connection: 2 x (3-wire)
- Sensor supply: 15 VDC
- Signal characteristics: Single-ended
- Signal type: Current
- Signal type (current): 0 … 20 mADC; 4 … 20 mADC; 3.6 … 21 mADC
- Supply voltage (field): 24 VDC; (Ex i power supply: Uo = max. 26.8 V); via power jumper contacts (power supply via blade contact; transmission via spring contact)
- Supply voltage (system): 5 VDC; via data contacts
- Temperature error (max.) of the upper-range value: ±0.01%/K
- Total number of channels (module): 4