Wago - 750-474
$455.00
Sale price
$455.00
Regular price
Standard analog input slice unit module - WAGO (750 series) - 2AI; 4-20mA; SE; 16-bits - 2I/O [2AI (2 x analog inputs (4-20mA; Single-ended; 15-bits / 80ms conversion; 2-wire / 3-wire))] - supply voltage 5Vdc (supplied by system) - with spring CAGE CLAMP connections - DIN-35 rail mounting (12mm width) - IP20 - rated for 0°C...+55°C ambient - equivalent to 750474
Specifications
- Primary brand: WAGO
- Functions: Standard analog input slice unit module
- Supply voltage (DC): 5Vdc (supplied by system)|18-31.2Vdc adjustable suppl. to field sensing devices
- Display: LED (A/C) green -- Function AI 1 / AI 2|LED (B/D) red -- Error AI 1 / AI 2
- Connection type: spring CAGE CLAMP connections
- Protection functions: overload protection|overvoltage protection|reverse polarity protection
- Mounting mode: DIN-35 rail
- Analog inputs: 2 x analog inputs (4-20mA; Single-ended; 15-bits / 80ms conversion; 2-wire / 3-wire)
- Measurement accuracy: +-0.1% (measuring error)|+-0.01% (temperature error)
- Dimensions: H100mm x W12mm x D69.8mm
- Net Width (mm): 12mm
- Material: Polycarbonate (PC) / Polyamide (PA) 6.6 housing
- Ambient air temperature for operation: 0°C...+55°C
- Ambient air temperature for storage: -40°C...+85°C
- Humidity: 95% relative humidity (RH; non-condensing)
- Mechanical resistance: Vibration resistance according to EN 60068-2-6 -- 4g|Shock resistance according to EN 60068-2-27 --15g
- Current consumption: 75mA (5Vdc; system supply)
- eClass code: 27-24-26-01
- ETIM code: EC001596
- Customs Tariff Number: 85389099990
- GTIN code: 4045454393281
- Order code / Manufacturer SKU: 750-474
- Manufacturer product status: Commercialized
- Equivalent to: 750474
- EAN code: 4045454393281
- Compliant with standard(s): CE|EMC immunity to interference|- EN 61000-6-2|- marine applications|EMC emission of interference|- EN 61000-6-4|- marine applications|General approvals|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03083|- KC - National Radio Research Agency - Article 58-2 / Clause 3 - certificate MSIP-REM-W43-AIM750|- UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 508 - certificate E175199|Declarations of conformity and manufacturer's declarations|- EU-Declaration of Conformity - WAGO GmbH & Co. KG|- UK-Declaration of Conformity - WAGO GmbH & Co. KG|Approvals for marine applications|- ABS - American Bureau of Shipping - certificate 22-2219060|- BSH - Bundesamt fuer Seeschifffahrt und Hydrographie - certificate 1104|- BV - Bureau Veritas S.A. - certificate 13453/E0 BV|- DNV - DNV GL SE - DNV-CG-0339 / Aug.2021 - certificate TAA0000194|- KR - Korean Register of Shipping - certificate KR HMB05880-AC001|- LR - Lloyds Register EMEA - certificate LR22180952TA|- PRS - Polski Rejestr Statkow - certificate TE/1101/880590/23|- RINA - RINA Germany GmbH - certificate ELE343521XG001|Approvals for hazardous areas|- ATEX - TUV Nord Cert GmbH - EN 60079-0 - certificate TUV14ATEX148929X (II 3 G Ex ec IIC T4 Gc)|- CCCEx - CQST/CNEx - CNCA-C23-01 - certificate 2020312310000213 (Ex ec IIC T4 Gc)|- IECEx - TUV Nord Cert GmbH - IEC 60079-0 - certificate IECEx TUN 14.0035 X (Ex ec IIC T4 Gc)|- INMETRO - TUV Rheinland do Brasil Ltda. - IEC 60079-0 - certificate TUV 12.1297 X|- UKEx - WAGO GmbH & Co. KG - EN 60079-0 - certificate UKCA_WAGO22UKEX003X_ec|- UL - Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS) - UL 121201 - certificate E198726|RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
- Location of origin: Germany
- Degree of pollution: 2
- Level 1 category: Automation components
- Level 2 category: Programmable Logic Controllers & components
- Level 3 category: I-O Units
- Product title: Standard analog input slice unit module - WAGO
Commercial data
- Country of origin: DE
- Customs tariff number: 85389099990
- ECCN: NO US CLASSIFICATION
- eCl@ss 10.0: 27-24-26-01
- eCl@ss 9.0: 27-24-26-01
- ETIM 8.0: EC001596
- ETIM 9.0: EC001596
- GTIN: 4045454393281
- Packaging type: box
- Product Group: 15 (I/O System)
- PU (SPU): 1 pcs
Connection data
- Connectable conductor materials: Copper
- Connection technology: inputs/outputs: 8 x CAGE CLAMP®
- Connection type 1: Inputs/Outputs
- Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
- Strip length: 8 … 9 mm / 0.31 … 0.35 inches
Environmental Product Compliance
- CAS-No.: 1303-86-2|1317-36-8|7439-92-1|80-43-3
- REACH Candidate List Substance: Diboron trioxide|Lead|Lead monoxide|Peroxide, bis(1-methyl-1-phenylethyl)
- RoHS Compliance Status: Compliant,With Exemption
- RoHS Exemption: 6(c)|7(a)|7(c)-I|7(c)-II
- SCIP notification number (Austria): 8b7cabf0-2cd3-4b94-a73b-220efe7637ab
- SCIP notification number (Belgium): 64998619-9c63-4aef-8424-08a9731dd0b9
- SCIP notification number (Bulgaria): 015eb609-f94e-4871-bedd-708d326594a8
- SCIP notification number (Czech Republic): 37ad1a74-e5b9-4261-971a-963ff93b5c68
- SCIP notification number (Denmark): 2b74c0cf-718b-4962-a1c8-167ef90f7f60
- SCIP notification number (Finland): e9b13a53-b1da-4f07-9382-fc34bfa722ad
- SCIP notification number (France): cbc9da82-872a-412b-857d-32c3ff56a3e2
- SCIP notification number (Germany): 61b222de-d4a1-495b-91bc-04e250e262c2
- SCIP notification number (Hungary): 3d46027c-a572-479c-b06b-4809717da8f7
- SCIP notification number (Italy): 129d03e0-9ea8-4e9b-9869-e4501c2b41c4
- SCIP notification number (Netherlands): d3d94746-27cb-4371-a0a4-21015aa9e49a
- SCIP notification number (Poland): f5e09e60-116f-48e4-b2b9-9e9ff51e640c
- SCIP notification number (Romania): db34ae3d-a842-431f-a7da-4d5aac50f6b1
- SCIP notification number (Sweden): 91f87b05-282c-44a2-910c-3cb43ea7cf18
Environmental requirements
- Ambient temperature (operation): 0 … +55 °C
- Ambient temperature (storage): -40 … +85 °C
- EMC emission of interference: per EN 61000-6-4, marine applications
- EMC immunity to interference: per EN 61000-6-2, marine applications
- Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
- Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
- Operating altitude: 0 … 2000 m / 0 … 6562 ft
-
Permissible H2S contaminant concentration at a relative humidity
75 %: 10ppm -
Permissible SO2 contaminant concentration at a relative humidity
75 %: 25ppm - Pollution degree: 2 per IEC 61131-2
- Protection type: IP20
- Relative humidity (without condensation): 95%
- Shock resistance: 15g per IEC 60068-2-27
- Vibration resistance: 4g per IEC 60068-2-6
Material data
- Color: light gray
- Conformity marking: CE
- Fire load: 1.048MJ
- Housing material: Polycarbonate; polyamide 6.6
- Weight: 53.2g
Mechanical data
- Mounting type: DIN-35 rail
Physical data
- Depth: 69.8 mm / 2.748 inches
- Depth from upper-edge of DIN-rail: 62.6 mm / 2.465 inches
- Height: 100 mm / 3.937 inches
- Width: 12 mm / 0.472 inches
Technical data
- Conversion time (typ.): 80ms
- Current consumption (5 V system supply): 75mA
- Data width: 2 x 16-bit data; 2 x 8-bit control/status (optional)
- Indicators: LED (A, C) green: Function AI 1, AI 2; LED (B, D) red: Error AI 1, AI 2
- Input filter frequency (analog): 50Hz
- Input resistance (max.): 220Ω
- Input voltage (max.): 24 V
- Input voltage (note): Non-linear, overload protected U = 1.2 V + 160 Ω x I meas
- Isolation: 500 V system/field
- Measurement error (reference temperature): 25°C
- Measurement error, deviation (max.) from the upper-range value: 0.1%
- Noise rejection above sampling frequency: -40dB
- Noise rejection at sampling frequency: -100dB
- Number of analog inputs: 2
- Number of incoming power jumper contacts: 2
- Number of outgoing power jumper contacts: 2
- Overvoltage protection: 30 V, reverse polarity protected
- Resolution [bit]: 15bits
- Sensor connection: 2 x (2-wire, 3-wire)
- Signal characteristics: Single-ended
- Signal type: Current
- Signal type (current): 4 … 20 mADC
- Supply voltage (field): 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission (field side supply voltage only) via spring contact)
- Supply voltage (system): 5 VDC; via data contacts
- Temperature error (max.) of the upper-range value: 0.01%/K
- Total number of channels (module): 2