Standard analog input slice unit module with diagnostics - WAGO (750 series) - 2AI; TC K; Diagn - 2I/O [2AI (2 x analog inputs (Thermocouple type K / 0.1°C resolution / 320ms conversion; 2-wire))] - supply voltage 5Vdc (supplied by system) - with spring CAGE CLAMP connections - DIN-35 rail mounting (12mm width) - IP20 - rated for 0°C...+55°C ambient - equivalent to 750469

Specifications

  • Primary brand: WAGO
  • Functions: Standard analog input slice unit module
  • Design: diagnostics
  • Supply voltage (DC): 5Vdc (supplied by system)
  • Display: LED (A/C) green -- Function AI 1 / AI 2|LED (B/D) red -- Error AI 1 / AI 2
  • Connection type: spring CAGE CLAMP connections
  • Mounting mode: DIN-35 rail
  • Analog inputs: 2 x analog inputs (Thermocouple type K / 0.1°C resolution / 320ms conversion; 2-wire)
  • Measurement accuracy: +-6K (voltage input; +-2K / cold junction compensation; +-4K)|+-0.2K/K
  • Dimensions: H100mm x W12mm x D69.8mm
  • Net Width (mm): 12mm
  • Material: Polycarbonate (PC) / Polyamide (PA) 6.6 housing
  • Ambient air temperature for operation: 0°C...+55°C
  • Ambient air temperature for storage: -40°C...+85°C
  • Humidity: 95% relative humidity (RH; non-condensing)
  • Mechanical resistance: Vibration resistance according to EN 60068-2-6 -- 4g|Shock resistance according to EN 60068-2-27 --15g
  • Current consumption: 65mA (5Vdc; system supply)
  • Customs Tariff Number: 85389099990
  • ETIM code: EC001596
  • eClass code: 27-24-26-01
  • GTIN code: 4045454393083
  • Order code / Manufacturer SKU: 750-469
  • Manufacturer product status: Commercialized
  • Equivalent to: 750469
  • EAN code: 4045454393083
  • Compliant with standard(s): CE|EMC immunity to interference|- EN 61000-6-2|- marine applications|EMC emission of interference|- EN 61000-6-4|- marine applications|General approvals|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03083|- KC - National Radio Research Agency - Article 58-2 / Clause 3 - certificate MSIP-REM-W43-AIM750|- UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 508 - certificate E175199|Declarations of conformity and manufacturer's declarations|- EU-Declaration of Conformity - WAGO GmbH & Co. KG|- UK-Declaration of Conformity - WAGO GmbH & Co. KG|Approvals for marine applications|- ABS - American Bureau of Shipping - certificate 22-2219060|- BSH - Bundesamt fuer Seeschifffahrt und Hydrographie - certificate 1104|- BV - Bureau Veritas S.A. - certificate 13453/E0 BV|- DNV - DNV GL SE - DNV-CG-0339 / Aug.2021 - certificate TAA0000194|- KR - Korean Register of Shipping - certificate KR HMB05880-AC001|- LR - Lloyds Register EMEA - certificate LR22180952TA|- PRS - Polski Rejestr Statkow - certificate TE/1101/880590/23|- RINA - RINA Germany GmbH - certificate ELE343521XG001|Approvals for hazardous areas|- ATEX - TUV Nord Cert GmbH - EN 60079-0 - certificate TUV14ATEX148929X (II 3 G Ex ec IIC T4 Gc)|- CCCEx - CQST/CNEx - CNCA-C23-01 - certificate 2020312310000213 (Ex ec IIC T4 Gc)|- IECEx - TUV Nord Cert GmbH - IEC 60079-0 - certificate IECEx TUN 14.0035 X (Ex ec IIC T4 Gc)|- INMETRO - TUV Rheinland do Brasil Ltda. - IEC 60079-0 - certificate TUV 12.1297 X|- UKEx - WAGO GmbH & Co. KG - EN 60079-0 - certificate UKCA_WAGO22UKEX003X_ec|- UL - Underwriters Laboratories Inc. (HAZARDOUS LOCATIONS) - UL 121201 - certificate E198726|RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
  • Location of origin: Germany
  • Degree of pollution: 2
  • Level 1 category: Automation components
  • Level 2 category: Programmable Logic Controllers & components
  • Level 3 category: I-O Units
  • Product title: Standard analog input slice unit module - diagnostics - WAGO

Commercial data

  • Country of origin: DE
  • Customs tariff number: 85389099990
  • ECCN: NO US CLASSIFICATION
  • eCl@ss 10.0: 27-24-26-01
  • eCl@ss 9.0: 27-24-26-01
  • ETIM 8.0: EC001596
  • ETIM 9.0: EC001596
  • GTIN: 4045454393083
  • Packaging type: box
  • Product Group: 15 (I/O System)
  • PU (SPU): 1 pcs

Connection data

  • Connectable conductor materials: Copper
  • Connection technology: inputs/outputs: 8 x CAGE CLAMP®
  • Connection type 1: Inputs/Outputs
  • Fine-stranded conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Solid conductor: 0.08 … 2.5 mm² / 28 … 14 AWG
  • Strip length: 8 … 9 mm / 0.31 … 0.35 inches

Environmental Product Compliance

  • CAS-No.: 1303-86-2|1317-36-8|7439-92-1
  • REACH Candidate List Substance: Diboron trioxide|Lead|Lead monoxide
  • RoHS Compliance Status: Compliant,With Exemption
  • RoHS Exemption: 6(c)|7(a)|7(c)-I|7(c)-II
  • SCIP notification number (Austria): 8de57f17-6cea-41c8-9428-dc8c69b36a3e
  • SCIP notification number (Belgium): fad3c483-4252-439f-87a6-5be0ca6fc3ca
  • SCIP notification number (Bulgaria): ca61cf7b-c621-44e4-9df8-125a8671cd5a
  • SCIP notification number (Czech Republic): b81380bb-4500-4d05-9c04-ad77be0cc4d6
  • SCIP notification number (Denmark): a705d607-9dac-4e28-af9a-6a5d2b8a1da9
  • SCIP notification number (Finland): 3302c55e-e82f-4ebe-a8f4-8743500f42ba
  • SCIP notification number (France): cc3e1fae-5840-4079-9c50-da64d7c8a8e2
  • SCIP notification number (Germany): e5c5d4db-35da-42fd-96d2-4f0655999d82
  • SCIP notification number (Hungary): e4007bf4-9f71-4d0b-a44b-b926b144db5b
  • SCIP notification number (Italy): af1cdaa9-40af-4bd7-b388-315c866af54d
  • SCIP notification number (Netherlands): 0d0b83d5-edf6-40a0-ad6c-8de098d39d4a
  • SCIP notification number (Poland): f13b6ffa-2258-4009-988f-4bf116c6bc2f
  • SCIP notification number (Romania): 4261d15a-45be-4df0-b894-edc007578c77
  • SCIP notification number (Sweden): da562e67-424b-42a1-97c8-3951d8b02112

Environmental requirements

  • Ambient temperature (operation): 0 … +55 °C
  • Ambient temperature (storage): -40 … +85 °C
  • EMC emission of interference: per EN 61000-6-4, marine applications
  • EMC immunity to interference: per EN 61000-6-2, marine applications
  • Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
  • Mounting position: Horizontal left, horizontal right, horizontal top, horizontal bottom, vertical top and vertical bottom
  • Operating altitude: 0 … 2000 m / 0 … 6562 ft
  • Permissible H2S contaminant concentration at a relative humidity 75 %: 10ppm
  • Permissible SO2 contaminant concentration at a relative humidity 75 %: 25ppm
  • Pollution degree: 2 per IEC 61131-2
  • Protection type: IP20
  • Relative humidity (without condensation): 95%
  • Shock resistance: 15g per IEC 60068-2-27
  • Vibration resistance: 4g per IEC 60068-2-6

Material data

  • Color: light gray
  • Conformity marking: CE
  • Fire load: 1.034MJ
  • Housing material: Polycarbonate; polyamide 6.6
  • Weight: 52g

Mechanical data

  • Mounting type: DIN-35 rail

Physical data

  • Depth: 69.8 mm / 2.748 inches
  • Depth from upper-edge of DIN-rail: 62.6 mm / 2.465 inches
  • Height: 100 mm / 3.937 inches
  • Width: 12 mm / 0.472 inches

Technical data

  • Cold junction compensation: at each pair of terminal blocks
  • Conversion time (typ.): 320ms
  • Current consumption (5 V system supply): 65mA
  • Data width: 2 x 16-bit data; 2 x 8-bit control/status (optional)
  • Indicators: LED (A, C) green: Function AI 1, AI 2; LED (B, D) red: Error AI 1, AI 2
  • Internal resistance: 1000kΩ
  • Isolation: 500 V system/field
  • Measurement error (25 °C): < ±6 K (voltage input < ±2 K; cold junction compensation < ±4 K)
  • Number of analog inputs: 2
  • Resolution (over entire range): 0.1 °C
  • Sensor connection: 2 x (2-wire)
  • Sensor types: Thermocouple K
  • Signal type: Thermocouple
  • Supply voltage (system): 5 VDC; via data contacts
  • Temperature coefficient: < ±0.2 K/K
  • Temperature range: −100 … +1370 °C