Skip to product information
Wago - 2857-533
$430.50
Sale price
$430.50
Regular price
RTD threshold value switch with DIP / software configuration + display - WAGO (2857 series) - with 1 x analog input (RTD Pt100 / Pt200 / Pt500 / Pt1000 / Pt5000 / Pt10000 / Pt10...Pt20000 / potentiometer; 0-100 kΩ; 2-wire / 3-wire / 4-wire) - supply voltage 16.8-31.2Vdc (24Vdc nom.) - with Push-in CAGE CLAMP spring connections - DIN-35 rail mounting (12.5mm width) - IP20 - rated for -40°C...+70°C ambient - equivalent to 2857533
Specifications
- Primary brand: WAGO
- Functions: RTD threshold value switch
- Design: DIP / software configuration|display
- Supply voltage (DC): 16.8-31.2Vdc (24Vdc nom.)
- Connection type: Push-in CAGE CLAMP spring connections
- Mounting mode: DIN-35 rail
- Digital outputs: 1 x digital output (NO rly. contact type; 250Vac; 6A)
- Analog inputs: 1 x analog input (RTD Pt100 / Pt200 / Pt500 / Pt1000 / Pt5000 / Pt10000 / Pt10...Pt20000 / potentiometer; 0-100 kΩ; 2-wire / 3-wire / 4-wire)
- Measurement accuracy: ≤ 0.01%/K (temperature coefficient)
- Dimensions: H110mm x W12.5mm x D107mm
- Net Width (mm): 12.5mm
- Material: Hard Gold-plated Silver-Nickel (AgNi + Au) contacts
- Ambient air temperature for operation: -40°C...+70°C
- Ambient air temperature for storage: -40°C...+85°C
- Current consumption: 40mA (24Vdc; at nominal load)
- Customs Tariff Number: 90303370000
- eClass code: 27-37-18-10
- ETIM code: EC001446
- GTIN code: 4050821676973
- Order code / Manufacturer SKU: 2857-533
- Manufacturer product status: Commercialized
- Equivalent to: 2857533
- EAN code: 4050821676973
- Compliant with standard(s): Safety and protection|- Overvoltage category -- II|CE|EN 50121-3-2|EN 61010-1|EN 61373|EMC immunity to interference|- EN 61000-6-2|- EN 61326-2-3|- EN 50121-3-2|EMC emission of interference|- EN 61000-6-4|- EN 61326-2-3|- EN 50121-3-2|General approvals|- EAC - GZO Almaty Standart - TP TC 004/2011 - certificate EAC CoC 03084|- EAC - GZO Almaty Standart - TP TC 020/2011 - certificate EAC CoC 03083|- UL - Underwriters Laboratories Inc. (ORDINARY LOCATIONS) - UL 61010-2-201 - certificate E175199|Declarations of conformity and manufacturer's declarations|- EU-Declaration of Conformity - WAGO GmbH & Co. KG|RoHS compliant with exemption (6(c) / 7(a) / 7(c)-I / 7(c)-II)
- Location of origin: Germany
- Degree of pollution: 2
- Level 1 category: Automation components
- Product title: RTD threshold value switch - WAGO
Commercial data
- Country of origin: DE
- Customs tariff number: 90303370000
- ECCN: NO US CLASSIFICATION
- eCl@ss 10.0: 27-37-18-10
- eCl@ss 9.0: 27-37-18-10
- ETIM 8.0: EC001446
- ETIM 9.0: EC001446
- GTIN: 4050821676973
- Packaging type: bag
- Product Group: 6 (INTERFACE ELECTRONIC)
- PU (SPU): 1 pcs
Connection data
- Connection technology: Push-in CAGE CLAMP®
- Fine-stranded conductor: 0.2 … 2.5 mm² / 24 … 12 AWG
- Solid conductor: 0.2 … 2.5 mm² / 24 … 12 AWG
- Strip length: 9 … 10 mm / 0.35 … 0.39 inches
- WAGO connector: picoMAX® 5.0
Environmental Product Compliance
- CAS-No.: 1303-86-2|1317-36-8|7439-92-1|75980-60-8|79-94-7
- REACH Candidate List Substance: 2,2',6,6'-tetrabromo-4,4'-isopropylidenediphenol|Diboron trioxide|Lead|Lead monoxide|Perfluorobutane sulfonic acid (PFBS) and its salts|Phosphine oxide, diphenyl(2,4,6-trimethylbenzoyl)-
- RoHS Compliance Status: Compliant,With Exemption
- RoHS Exemption: 6(c)|7(a)|7(c)-I|7(c)-II
- SCIP notification number (Austria): 5dacf9f1-acec-4030-a576-2066861dd611
- SCIP notification number (Belgium): 93a2e53f-f28c-4be6-803b-f05ac560dbc3
- SCIP notification number (Bulgaria): 2674e09f-f188-47ca-907f-6da7555f3cbe
- SCIP notification number (Czech Republic): 53482b4c-731d-46d7-978a-76349083b4ae
- SCIP notification number (Denmark): bd15bcb7-0805-48fd-804d-7c2b0575624e
- SCIP notification number (Finland): f95a8eb7-dda8-4f0f-a6a7-71055557790a
- SCIP notification number (France): a95114a5-e653-4a5c-9d8d-4217bd36673b
- SCIP notification number (Germany): 5058fdd7-a366-4ffa-9b3b-8dc6348e2b84
- SCIP notification number (Hungary): 53cffea9-5596-4742-9f5a-4a850f720b5b
- SCIP notification number (Italy): d49bce73-6715-4d98-b444-679711c15ee3
- SCIP notification number (Netherlands): 0175bf0f-8d9e-4f18-afd7-43d4440d1d8d
- SCIP notification number (Poland): 07e60571-bb7b-447a-90ca-0a5fc4588e2a
- SCIP notification number (Romania): b18f85a9-7d9d-48f3-824e-f73837ce0f15
- SCIP notification number (Sweden): e18be451-767b-4edb-abbc-451ebe189c33
Environmental requirements
- Ambient temperature (operation): -40 … +70 °C
- Ambient temperature (storage): -40 … +85 °C
- Temperature range of connection cable: ≥ (Tambient + 10 K)
- Temperature range of connection cable (UL): 80°C
Material data
- Fire load: 1.573MJ
- Weight: 86.6g
Mechanical data
- Mounting type: DIN-35 rail
Notes
- Note: This product is supplied with 24 VDC, which can be commoned using lateral push-in type jumper bars: (6.1) US+ (BR) and (6.2) GND 2 (BR). With this variant, it is necessary to ensure that the maximum permissible total current of 6 A is not exceeded.|Additional setting options via the WAGO Interface Configuration Software|This product is supplied with 24 VDC, which can be commoned using lateral push-in type jumper bars: (6.1) US+ (BR) and (6.2) GND 2 (BR). With this variant, it is necessary to ensure that the maximum permissible total current of 6 A is not exceeded.|Additional setting options via WAGO Interface Configuration Software or WAGO Interface Configuration App
Physical data
- Depth from upper-edge of DIN-rail: 107 mm / 4.213 inches
- Height: 110 mm / 4.331 inches
- Width: 12.5 mm / 0.492 inches
Safety and protection
- Insulation coordination (UL) - Insulation type (input, supply and service interface/relay output): Reinforced insulation (safe isolation)
- Insulation coordination (UL) - Insulation type (input/supply/service interface): Basic insulation
- Insulation coordination (UL) - Overvoltage category: II
- Insulation coordination (UL) - Pollution degree: 2
- Measurement category per EN/UL 61010-2-030: CAT II (input)
- Note on insulation parameters: Temperature sensors are not intended for use in dangerous circuits, provided the external temperature sensors used do not have basic insulation in accordance with EN/UL 61010-1 (300 VAC; overvoltage category II; pollution degree 2). The digital output (DO) is at the potential of the supply.|Temperature sensors are not intended for use in dangerous circuits, provided the external temperature sensors used do not have basic insulation in accordance with EN/UL 61010-1 (300 VAC; overvoltage category II; pollution degree 2).|The digital output (DO) is at the potential of the supply.
- Protection type: IP20
- Rated voltage: 300V
- Rated voltage of the measurement circuit connections per EN 61010-2-030: AC 300 V
- Test voltage - Test voltage (input/relay output/supply): 4 kVAC; 60 Hz; 1 min
- Test voltage - Test voltage (input/service interface): 3 kVAC; 60 Hz; 1 min
- Test voltage - Test voltage (relay output/service interface): 4 kVAC; 60 Hz; 1 min
- Test voltage - Test voltage (supply/service interface): 2.5 kVAC; 60 Hz; 1 min
Standards and specifications
- Conformity marking: CE
- EMC emission of interference: EN 61000-6-4; EN 61326-2-3; EN 50121-3-2
- EMC immunity to interference: EN 61000-6-2; EN 61326-2-3; EN 50121-3-2
- Standards/specifications: EN 61010-1|EN 61373|EN 50121-3-2|EN 50121-3-2|EN 61010-1|EN 61373
Technical data
- Configuration - Configuration options: WAGO Configuration Display|DIP switch|WAGO Interface Configuration Software|WAGO Interface Configuration App|WAGO Configuration Display
- Input - Input signal type: Potentiometer|Resistance|RTD sensors|Potentiometers|Resistor
- Input (resistors) - Input range (potentiometer): 0 … 100 kΩ
- Input (resistors) - Input range (resistor): 0 … 100 kΩ
- Input (RTD sensors) - Sensor connection: 2-wire; 3-wire; 4-wire; differential
- Input (RTD sensors) - Sensor power supply (RTD) max.: ≤ 0.5 mA
- Input (RTD sensors) - Sensor types (RTD): Pt100|Pt200|Pt500|Pt1000|Pt5000|Pt10000|Pt10 … Pt20000
- Input (RTD sensors) - Temperature measurement range (RTD): -200 … +850 °C
- Measurement error - Temperature coefficient: ≤ 0.01 %/K
- Measurement error - Transmission error (max.): ± 1 K
- Operating data - Continuous current (max.): 6 A
- Output (digital) - Configurable rise/fall delay time (DO): 0 … 60 s (via software)
- Output (digital) - Continuous current (DO) max.: 100 mA (no internal restriction)
- Output (digital) - Number of switching thresholds (DO): 1 or 2 (adjustable)
- Output (digital) - Switching voltage (DO) max.: Supply voltage (applied) - 0.3 V
- Output (relay) - Bounce time (typ.): 8ms
- Output (relay) - Configurable rise/fall delay time (relay): 0 … 60 s (via software)
- Output (relay) - Contact material (relay): AgNi + Au
- Output (relay) - Dielectric strength (open contact) (AC, 1 min): 1kVrms|1 kVrms
- Output (relay) - Drop-out time (typ.): 4ms
- Output (relay) - Number of make/switch-on contacts: 1
- Output (relay) - Number of switching thresholds (relay): 1 or 2 (adjustable)
- Output (relay) - Pull-in time (typ.): 8ms
- Output (relay) - Switching Voltage, Max.: 250 VAC
- Power supply - Current consumption at nominal supply voltage: ≤ 40 mA (+ IDO)
- Power supply - Nominal supply voltage US: DC 24 V (SELV)
- Power supply - Power supply type: 24 VDC
- Power supply - Supply voltage range: ±30 %
- Signal processing - Hysteresis: Adjustable via DIP switch or software
- Signal processing - Software filter (adjustable): Moving average value (filter level: 30)
- Signal processing - Step response (typ.): 60 ms (2-wire)|360 ms (3-wire)|540 ms (4-wire)|360 ms (potentiometer)