Wago - 2006-1621
$12.73
Sale price
$12.73
Regular price
Feed-through/thru terminal block with 1-deck/level + fused-disconnect (lever type; 5x30mm) + side/lateral and center marking slots - WAGO (2006 TOPJOB S series) - Gray - 1 feed-through pole (1P) / 2-wires (1 push-in + 1 push-in) (1+1) - 6mm2 nominal cross-section - for 0.5mm2...10mm2 / for #20AWG...#8AWG - Rated current 10A - with Push-in CAGE CLAMP spring connections - DIN-35 rail (35 x 15 / 35 x 7.5) mounting (7.5mm width) - equivalent to 20061621
Specifications
- Primary brand: WAGO
- Functions: Feed-through/thru terminal block
- Design: 1-deck/level|fused-disconnect (lever type; 5x30mm)|side/lateral and center marking slots|2 jumper slots
- Poles: 1 feed-through pole (1P)
- Temperature: Processing temperature -35°C...+85°C|Continuous operating temperature -60°C...+105°C
- Rated current: (IEC) 10A|(UL) 15A|(CSA) 15A
- Color: Gray
- Connection capacity: 2-wires (1 push-in + 1 push-in) (1+1)
- Rated operating voltage (Ue): (IEC) 800V|(UL) 600V|(CSA) 600V
- Rated impulse voltage (Uimp): (IEC) 8kV
- Connection type: Push-in CAGE CLAMP spring connections
- Cross-section: for 0.5mm2...10mm2 fine stranded or solid conductors|for 0.5mm2...6mm2 fine stranded conductors with insulated ferrule|for 2.5mm2...6mm2 fine stranded conductors with ferrule; push-in termination|for 1mm2...10mm2 solid conductors; push-in termination|for #20AWG...#8AWG fine stranded or solid conductors|for #20AWG...#10AWG fine stranded conductors with insulated ferrule|for #16AWG...#10AWG fine stranded conductors with ferrule; push-in termination|for #14AWG...#8AWG solid conductors; push-in termination|6mm2 nominal cross-section
- Mounting mode: DIN-35 rail (35 x 15 / 35 x 7.5)
- Dimensions: H96.3mm x W7.5mm x D59mm
- Net Width (mm): 7.5mm
- Material: Polyamide (PA) 66
- GTIN code: 4045454821173
- Customs Tariff Number: 85369095000
- eClass code: 27-14-11-16
- ETIM code: EC000899
- Order code / Manufacturer SKU: 2006-1621
- Manufacturer product status: Commercialized
- Equivalent to: 20061621
- EAN code: 4045454821173
- Compliant with standard(s): General approvals|- CCA - DEKRA Certification B.V. - EN 60947 - certificate NTR NL 7925/1|- CCA - DEKRA Certification B.V. - IEC 60947 - certificate 71-122840 REV.1|- CSA - DEKRA Certification B.V. - C22.2 No. 158 - certificate 1543858|- UR - Underwriters Laboratories Inc. - UL 1059 - certificate E45172|Declarations of conformity and manufacturer's declarations|- EU-Declaration of Conformity - WAGO GmbH & Co. KG|- Railway - WAGO GmbH & Co. KG - certificate Railway Ready|- UK-Declaration of Conformity - WAGO GmbH & Co. KG|Approvals for marine applications|- ABS - American Bureau of Shipping - EN 60947 - certificate 20-HG1941090-PDA|- DNV GL - Det Norske Veritas Germanischer Lloyd - certificate TAE00001V2|- LR - Lloyds Register - EN 60947 - certificate 91/20112 (E9)|RoHS compliant|material group I|V-0 flammability rating
- Location of origin: China
- Level 1 category: Electrical components
- Level 2 category: Terminal blocks
- Product title: Feed-through/thru terminal block - 1-deck/level - WAGO (TOPJOB S series)
Commercial data
- Country of origin: CN
- Customs tariff number: 85369095000
- ECCN: NO US CLASSIFICATION
- eCl@ss 10.0: 27-14-11-16
- eCl@ss 9.0: 27-14-11-16
- ETIM 8.0: EC000899
- ETIM 9.0: EC000899
- GTIN: 4045454821173
- Packaging type: box
- Product Group: 22 (TOPJOB S)
- PU (SPU): 25 pcs
Connection data
- Clamping units: 2
- Connection 1 - Actuation type: Operating tool
- Connection 1 - Connectable conductor materials: Copper
- Connection 1 - Connection technology: Push-in CAGE CLAMP®
- Connection 1 - Fine-stranded conductor: 0.5 … 10 mm² / 20 … 8 AWG
- Connection 1 - Fine-stranded conductor; with ferrule; push-in termination: 2.5 … 6 mm² / 16 … 10 AWG
- Connection 1 - Fine-stranded conductor; with insulated ferrule: 0.5 … 6 mm² / 20 … 10 AWG
- Connection 1 - Nominal cross-section: 6 mm²
- Connection 1 - Note (conductor cross-section): Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
- Connection 1 - Solid conductor: 0.5 … 10 mm² / 20 … 8 AWG
- Connection 1 - Solid conductor; push-in termination: 1 … 10 mm² / 14 … 8 AWG
- Connection 1 - Strip length: 13 … 15 mm / 0.51 … 0.59 inches
- Connection 1 - Wiring direction: Front-entry wiring
- Number of jumper slots: 2
- Number of levels: 1
- Total number of potentials: 1
Electrical data
- General information - Fuse receptacle: pivoting
- General information - Fuse type: Cylindrical fuse; 5 x 30 mm
- Power Loss - Power loss (max.) Pl (max.) (note): When selecting glass cartridge fuses, make sure that the maximum power loss listed below is not exceeded. The power loss is determined according to IEC or EN 60947-7-3/VDE 0611-6 at 23°C. The temperature rise of the terminal block must be checked according to their application and mounting. Higher ambient temperatures represent an additional impact on miniature fuses. Therefore, in such applications, the rated current must be reduced if necessary. More details are available from the manufacturers.
- Power Loss - Power loss Pl max. overload and short-circuit protection (group arrangement): 1.6W
- Power Loss - Power loss Pl max. overload and short-circuit protection (individual arrangement): 1.6W
- Power Loss - Power loss Pl max. short-circuit protection (group arrangement): 2.5W
- Power Loss - Power loss Pl max. short-circuit protection (individual arrangement): 2.5W
- Ratings per CSA - Approvals per: CSA 22.2 No 158
- Ratings per CSA - Rated current CSA (Use Group B): 15A
- Ratings per CSA - Rated current CSA (Use Group C): 15A
- Ratings per CSA - Rated voltage CSA (Use Group B): 600V
- Ratings per CSA - Rated voltage CSA (Use Group C): 600V
- Ratings per IEC/EN - Legend (ratings): (III / 3) ≙ Overvoltage category III / Pollution degree 3
- Ratings per IEC/EN - Nominal voltage (III/3): 800V
- Ratings per IEC/EN - Rated current: 10A
- Ratings per IEC/EN - Rated impulse withstand voltage (III / 3): 8kV
- Ratings per IEC/EN - Ratings per: IEC/EN 60947-7-3
- Ratings per IEC/EN – Notes - Ratings (note): Electrical ratings are given by the fuse.
- Ratings per UL - Approvals per: UL 1059
- Ratings per UL - Rated current UL (Use Group B): 15A
- Ratings per UL - Rated current UL (Use Group C): 15A
- Ratings per UL - Rated voltage UL (Use Group B): 600V
- Ratings per UL - Rated voltage UL (Use Group C): 600V
Environmental Product Compliance
- RoHS Compliance Status: Compliant,No Exemption
Environmental requirements
- Continuous operating temperature: -60 … +105 °C
- Environmental Testing (Environmental Conditions) - Acceleration: 0.101g (highest test level used for all axes)|0.572g (highest test level used for all axes)|5g (highest test level used for all axes)
- Environmental Testing (Environmental Conditions) - Extended test scope: Monitoring for contact faults/interruptions: Passed|Passed
- Environmental Testing (Environmental Conditions) - Extended test scope: Voltage drop measurement before and after each axis: Passed|Passed
- Environmental Testing (Environmental Conditions) - Frequency: f1 = 5 Hz to f2 = 150 Hz|f1 = 5 Hz to f2 = 150 Hz
- Environmental Testing (Environmental Conditions) - Function test with noise-like vibration: Test passed according to Section 8 of the standard
- Environmental Testing (Environmental Conditions) - Monitoring for contact faults/interruptions: Passed
- Environmental Testing (Environmental Conditions) - Number of shocks per axis: 3 pos. und 3 neg.
- Environmental Testing (Environmental Conditions) - Shock duration: 30 ms
- Environmental Testing (Environmental Conditions) - Shock form: Half sine
- Environmental Testing (Environmental Conditions) - Shock test: Test passed according to Section 10 of the standard
- Environmental Testing (Environmental Conditions) - Simulated service life test through increased levels of noise-like vibration: Test passed according to Section 9 of the standard
- Environmental Testing (Environmental Conditions) - Spectrum/Installation location: Service life test, Category 1, Class A/B
- Environmental Testing (Environmental Conditions) - Test directions: X, Y and Z axes|X, Y and Z axes|X, Y and Z axes
- Environmental Testing (Environmental Conditions) - Test duration per axis: 10 min.|5 h
-
Environmental Testing (Environmental Conditions) - Test procedure
Railway applications –
Rolling stock equipment –
Shock and vibration tests: DIN EN 61373 (VDE 0115-0106):2011-04 -
Environmental Testing (Environmental Conditions) - Test specification
Railway applications –
Rolling stock –
Electronic equipment: DIN EN 50155 (VDE 0115-200):2022-06 - Environmental Testing (Environmental Conditions) - Vibration and shock stress for rolling stock equipment: Passed
- Environmental Testing (Environmental Conditions) - Voltage drop measurement before and after each axis: Passed
- Processing temperature: -35 … +85 °C
Material data
- Color: gray
- Fire load: 0.456MJ
- Flammability class per UL94: V0
- Insulation material (main housing): Polyamide (PA66)
- Material group: I
-
Note (material data):
Information on material specifications can be found here
- Weight: 24.7g
Mechanical data
- Marking level: Center/side marking
- Mounting type: DIN-35 rail
Physical data
- Depth from upper-edge of DIN-rail: 59 mm / 2.323 inches
- Height: 96.3 mm / 3.791 inches
- Width: 7.5 mm / 0.295 inches